WIRING GUIDELINES

Terminal Layout

6

+

11

A/A'

 

1

C

NO

 

 

 

 

OUT 2

 

 

OUT 1

 

A) Measuring Inputs

NOTE: Any external components (like Zener diodes, etc.) connected between sensor and input terminals may cause errors in measurement due to excessive and/or not balanced line resistance or possible leakage cur- rents.

TC Input

7

NO

12 B/B'

C

2

 

 

 

_

RS485

 

 

 

 

 

 

 

8

 

13

C

NC

3

 

 

RTD

 

 

4

9

 

14

 

 

10

9

+

_

Shield

_

LINEAR

 

LINEPWR 100/240Vac Vac/dc24

 

TC

DIG 1

 

10

15

5

+

10

9

+

_

Shield

NOTE: When a relay output is used to drive an inductive load, connect an external snubber network (RC) across the terminals:

 

 

R

C

 

in accordance with the following table:

 

 

 

 

 

 

Load

C

 

R

P

Resistor and

Current

(F)

 

()

(W)

Capacitor Voltage

 

 

 

 

 

 

< 40 mA

0.047

 

100

1/2

260 Vac

 

 

 

 

 

 

< 150 mA

0.1

 

22

2

260 Vac

 

 

 

 

 

 

< 0.5 Amp

0.33

 

47

2

260 Vac

 

 

 

 

 

 

7

NOTE:

1)Do not run input wires with power cables.

2)For TC wiring use proper compensating cable, preferably shielded (see Thermocouple Compen- sating Cable Color Codes).

3)Shielded cable should be grounded at one end only.