SSI America 7SL instruction manual Default Parameters, Loading Default Operating Parameters, Off

Models: 7SL

1 36
Download 36 pages 19.88 Kb
Page 24
Image 24

DEFAULT PARAMETERS

Loading Default Operating Parameters

The control parameters can be loaded with predeter- mined default values. These are the settings loaded into the instrument prior to shipment from the factory. To load the default values proceed as follows:

a)Press and hold the key and press the key; the displays will show:

b) Press either the or key; the display will show:

c) Press the "FUNC" key; the display will show:

This indicates that the loading procedure has been initiated. After about 3 seconds the loading procedure is complete and the instrument reverts to the “Normal Display Mode.” The following is a list of the default operating parameters loaded during the procedure:

Default Operating Parameters List

Parameter

Default Value

Alarm Acknowledge

OFF

Software Key

Unlock

Setpoint Threshold

Low range value (if low limit)

 

High range value (if high or high/

 

low limit)

Setpoint1 Threshold

Low range value

Setpoint Threshold

 

Hysteresis

0.1%

Alarm Threshold

Low range (if process alarm)

 

100 (if deviation or band alarm)

Alarm Hysteresis

0.1%

Loading Default Configuration Parameters

The configuration parameters can be loaded with prede- termined default values. These are the settings loaded into the instrument prior to shipment from the factory. To load the default values proceed as follows:

a)Internal switch V101 must be open.

b)The upper display will show:

c)Press the key; the lower display will show the firmware version.

2 4

7sl-4-00.p65

24

9/17/02, 2:42 PM

Page 24
Image 24
SSI America 7SL Default Parameters, Loading Default Operating Parameters, Default Operating Parameters List, Off