Procedure

Switch on the instrument; the upper display will show “COnf”. Press the button; the upper display will show “CAL”.

Using the and pushbuttons (buttons), it is possible to select between ON and OFF. To go to the next parameter without modifying the calibration, press the FUNC button when the display shows “OFF”. To enter a calibration value, press the FUNC button when the dis- play shows “ON”.

Press the FUNC button to show the first calibration code on the lower display. Repeatedly press the FUNC button until the desired calibration (parameter) code appears.

FUNC button. When this calibration is complete, the instrument will go to the next parameter.

tH TC Input Final Scale Value

a)Set the calibrator to 60.000 mV.

b)Push the button; the displays will show “ON” and “tH”.

c)After a few seconds, start calibration by pressing the FUNC button. When this calibration is complete, the instrument will go to the next parameter.

t.TC Input Check

The display (Figure 3) shows “t.” followed by a number showing the measured value in counts:

NOTE: by pushing the SMRT button it is possible to go back to a previous parameter without memorizing the new calibration.

Entering Calibration Values

Following is a detailed, sequential procedure for entering and checking values for each calibration parameter:

tL

TC Input Initial Scale Value

a)Connect calibrator and instrument as shown in Figure 2.

10

9

Figure 2. Calibrator Connection

b)The upper display shows “OFF”, the lower displays shows “tL”.

c)Set calibrator to 0.000 mV.

d)Push the button; the display changes to “ON”.

e)After a few seconds, start calibration by pushing the

t.300

00

Figure 3. TC Calibration Check Display

a)Check the calibration (linear) by setting:

0.000 mV – the readout must be equal to “t.000 00” ± 10 counts;

60.000 mV – the readout must be equal to “t.300 00” ± 10 counts;

30.000 mV – the readout must be equal to “t.150 00” ± 10 counts.

b)Push the FUNC button to go to the next parameter.

rJ Cold Junction Compensation

NOTE: Make sure tL and tH are correctly calibrated before attempting rJ calibration.

a)Measure the temperature close to terminals 9 and 10 using an appropriate instrument – for example, MEMOCAL. See Figure 4.