State Industries SUF100199, SUF100150 manual Direct Venting ALL Models

Models: SUF100199 SUF100150

1 38
Download 38 pages 13.09 Kb
Page 14
Image 14

ULTRAFORCE COMMERCIAL GAS WATER HEATER

SUF 120 thru 400 SERVICE HANDBOOK

DIRECT VENTING – ALL MODELS

The air intake provided on the unit contains a mesh screen to prevent large particles from entering the unit. WHEN THE UNIT IS TO BE SET UP AS A DIRECT VENT, THE BALANCE PLATE AND MESH

SCREEN MUST BE REMOVED BEFORE GLUING PIPE TO THE CONNECTOR. THE INLET VENT PIPE MAY THEN BE GLUED TO THE AIR INTAKE PROVIDED ON THE UNIT.

45° PVC Elbow

Remove the balance plate and mesh screen before gluing intake air pipe to the fitting.

3” 120-250

4” 300- 400

Two 3” or 4” 45° PVC elbows with mesh screens are provided with each unit. Both elbows are to be used in direct vent applications. The screens are provided to keep vermin and large debris from entering the intake air and exhaust vent runs.

State Water Heaters – Technical Training Department 13

Ashland City, Tennessee © 2009

Servicing should only be performed by a Qualified Service Agent

198152-002

Page 14
Image 14
State Industries SUF100199, SUF100150 manual Direct Venting ALL Models