ULTRAFORCE COMMERCIAL GAS WATER HEATER

SUF 120 thru 400 SERVICE HANDBOOK

ADJUSTING TANK TEMPERATURE – OPERATING SET POINT - DIFFERENTIAL

The Operating Set Point of this water heater determines the regulated temperature for the water in the tank. This parameter is adjusted in the desktop Temperature menu. Items in this menu allow you to monitor different temperature readings in the tank along with adjusting the Operating Set Point and

Differential.

ACTION:

From the desktop screen, press Menu.

DISPLAY:

ACTION:

From the Main Menu, press Select to enter the "Temperatures" screen.

ACTION:

Press Change then use the UP and DOWN buttons to change the temperature Set Point.

DISPLAY:

Note: This procedure can also be used to change the Differential. The tank Upper and Lower Temperatures are not user changeable. They are determined by the temperature probes on the heater.

ACTION:

Press Update to accept the change or Cancel to reset it.

DISPLAY:

DISPLAY:

State Water Heaters – Technical Training Department 15

Ashland City, Tennessee © 2009

Servicing should only be performed by a Qualified Service Agent

198152-002