ULTRAFORCE COMMERCIAL GAS WATER HEATER

SUF 120 thru 400 SERVICE HANDBOOK

VARIABLE FREQUENCY DRIVE - BLOWER SPEED AND PRESSURE READINGS

The instructions for the VFD are sent from the CCB to in the form of a DC current. The chart below lists the current readings, the frequency signal displayed by the VFD, and the pressure switch settings needed for the CCB to let the burner operate. The frequency numbers displayed may vary slightly with slight variations in the DC voltage generated by the CCB. If the water heater exhibits poor run characteristics check the frequency display. If the frequency is more than 5% out of range, check the DC volt signal at the terminals shown on page 33.

Voltage – Frequency – Speed Instructions - VFD

Model

SUF

 

 

 

 

 

 

400

 

 

 

 

 

 

 

 

 

 

 

 

Instruction Volts DC

0 – 10

 

 

 

 

 

Terminals 0V and AI1

VDC

 

 

 

 

 

 

 

 

 

 

 

 

 

Volts

 

Frequency

Pressure

 

 

 

 

 

 

W.C.”

 

 

 

 

 

 

 

 

 

Ignition (low speed)

7.53

 

150 Hz+/- 2

5.3”

 

 

 

 

 

 

 

 

 

Purge (high speed)

7.77

 

155 Hz+/- 2

5.85”

 

 

 

 

 

 

 

 

 

VFD Part Number

197500-000

 

 

 

 

 

 

 

 

 

 

 

155

Frequency is displayed in the red LED. 155Hz

State Water Heaters – Technical Training Department 34

Ashland City, Tennessee © 2009

Servicing should only be performed by a Qualified Service Agent

198152-002

Page 35
Image 35
State Industries SUF100150, SUF100199 manual Variable Frequency Drive Blower Speed and Pressure Readings, Suf, 400