E6581429
2.Connection of equipment
2.1Cautions on wiring
QWiring |
|
|
|
|
|
|
| |
• Following power terminals are cage type ones. |
|
|
|
|
| |||
- Input terminals of |
|
|
|
|
| |||
- All power terminals of |
|
|
| |||||
For tightening torque and cable stripping length, refer to 1.3.1 2). |
|
|
| |||||
• For power terminal other than above, use sleeved pressure terminal to connect. This is because the space between |
| |||||||
terminals is small. Connect sleeved pressure terminals so that adjacent terminals do not touch each other. |
| |||||||
• For ground terminal, use wires of the size that is equivalent to or larger than those given in table below and always |
| |||||||
ground the inverter. |
|
|
|
|
| |||
|
|
|
| 2 | ||||
Use as large as and short a ground wire as possible and wire it as close as possible to the inverter. | ||||||||
| Voltage class | Applicable Motor |
| Grounding wire size |
| Grounding wire size |
| |
|
| (AWG) [Note] |
| (mm2) [Note] |
|
| ||
|
| 0.75~7.5kW |
| 14 |
| 2.5 |
|
|
|
| 11kW |
| 12 |
| 4 |
|
|
| 400V | 15, 18.5kW |
| 10 |
| 6 |
|
|
| 22kW |
| 10 |
| 10 |
|
| |
|
| 30~45kW |
| 4 |
| 16 |
|
|
|
| 55, 75kW |
| 2 |
| 35 |
|
|
|
| 90kW |
| 2 |
| 50 |
|
|
Note1: The recommended cable size is that of the cable (e.g. 600V class, HIV cable) with continuous maximum permissible temperature of 75°C. The ambient temperature is assumed to be 40°C or below. (The interconnect cable length is assumed to be 30m or less.)