E6581429

2.Connection of equipment

2.1Cautions on wiring

QWiring

 

 

 

 

 

 

 

• Following power terminals are cage type ones.

 

 

 

 

 

- Input terminals of VFPS1-4007PDE to 4220PDE

 

 

 

 

 

- All power terminals of VFPS1-4300PLE to 4900PLE, VFPS1-4300PDE to 4900PDE

 

 

 

For tightening torque and cable stripping length, refer to 1.3.1 2).

 

 

 

• For power terminal other than above, use sleeved pressure terminal to connect. This is because the space between

 

terminals is small. Connect sleeved pressure terminals so that adjacent terminals do not touch each other.

 

• For ground terminal, use wires of the size that is equivalent to or larger than those given in table below and always

 

ground the inverter.

 

 

 

 

 

 

 

 

 

2

Use as large as and short a ground wire as possible and wire it as close as possible to the inverter.

 

Voltage class

Applicable Motor

 

Grounding wire size

 

Grounding wire size

 

 

 

(AWG) [Note]

 

(mm2) [Note]

 

 

 

 

0.75~7.5kW

 

14

 

2.5

 

 

 

 

11kW

 

12

 

4

 

 

 

400V

15, 18.5kW

 

10

 

6

 

 

 

22kW

 

10

 

10

 

 

 

 

30~45kW

 

4

 

16

 

 

 

 

55, 75kW

 

2

 

35

 

 

 

 

90kW

 

2

 

50

 

 

Note1: The recommended cable size is that of the cable (e.g. 600V class, HIV cable) with continuous maximum permissible temperature of 75°C. The ambient temperature is assumed to be 40°C or below. (The interconnect cable length is assumed to be 30m or less.)