E6581429
QSelection of wiring equipment
Applicable motor | Inverter type form | Input current [A] | Magnetic contactor (MC) | ||
(kW) | Rated current [A] | Rated current [A] | |||
|
| ||||
0.75 | 1.8 | 4 | 25 | ||
1.5 | 3.5 | 6.3 | 25 | ||
2.2 | 5 | 10 | 25 | ||
3.7 | 8.8 | 14 | 25 | ||
5.5 | 11.4 | 25 | 25 | ||
7.5 | 15.8 | 25 | 25 | ||
11 | 21.9 | 30 | 32 | ||
15 | 30.5 | 40 | 40 | ||
18.5 | 37.5 | 60 | 50 | ||
22 | 43.6 | 60 | 50 | ||
30 | 56.7 | 100 | 80 | ||
37 | 69.5 | 100 | 125 | ||
45 | 85.1 | 125 | 125 | ||
55 | 104.8 | 150 | 125 | ||
75 | 140.3 | 200 | 250 | ||
90 | 171.8 | 200 | 250 |
(*1): Selections for use of the Toshiba
(*2): Choose the MCCB according to the power supply capacity.
For comply with UL and CSA standard, use the fuse certified by UL and CSA.
(*3): When using on the motor side during
(*4): Attach surge killers to the magnetic contactor and exciting coil of the relay.
(*5): In the case the magnetic contactor (MC) with
8