StreamLight VF-PS1 instruction manual Selection of wiring equipment, Rated current a AC-1

Models: VF-PS1

1 52
Download 52 pages 10.14 Kb
Page 44
Image 44

E6581429

QSelection of wiring equipment

Applicable motor

Inverter type form

Input current [A]

No-fuse breaker (MCCB)

Magnetic contactor (MC)

(kW)

Rated current [A]

Rated current [A] AC-1

 

 

0.75

VFPS1-4007PLE/PDE

1.8

4

25

1.5

VFPS1-4015PLE/PDE

3.5

6.3

25

2.2

VFPS1-4022PLE/PDE

5

10

25

3.7

VFPS1-4037PLE/PDE

8.8

14

25

5.5

VFPS1-4055PLE/PDE

11.4

25

25

7.5

VFPS1-4075PLE/PDE

15.8

25

25

11

VFPS1-4110PLE/PDE

21.9

30

32

15

VFPS1-4150PLE/PDE

30.5

40

40

18.5

VFPS1-4185PLE/PDE

37.5

60

50

22

VFPS1-4220PLE/PDE

43.6

60

50

30

VFPS1-4300PLE/PDE

56.7

100

80

37

VFPS1-4370PLE/PDE

69.5

100

125

45

VFPS1-4450PLE/PDE

85.1

125

125

55

VFPS1-4550PLE/PDE

104.8

150

125

75

VFPS1-4750PLE/PDE

140.3

200

250

90

VFPS1-4900PLE/PDE

171.8

200

250

(*1): Selections for use of the Toshiba 4-pole standard motor with power supply voltage of 400V-50Hz.

(*2): Choose the MCCB according to the power supply capacity.

For comply with UL and CSA standard, use the fuse certified by UL and CSA.

(*3): When using on the motor side during commercial-power supply operation, choose the MC with class AC-3 rated current for the motor rated current.

(*4): Attach surge killers to the magnetic contactor and exciting coil of the relay.