6.1Standard setting

The XP-COMPACT (except for 60Hz versions) is equipped with a Flash processor fitted out with EEPROM Memory, which means that even when it is disconnected from the battery, the parame- ters that were programmed for the application remain after a new connection to the battery.

It is possible to reinitialize (RESET) the XP-COMPACT by pressing simultaneously on the three push buttons 19/20/21 during at least 2 seconds. A beep will confirm the RESET. The inverter switches off after this operation. It can be turned on again after the beep. The programmed pa- rameters will remain.

The XP-COMPACT is delivered with the following default setting:

6.1.1Battery voltage

Low voltage

11.6V / 23.2V / 46.4V

Float Charge

13.5V / 27.0V / 54.0V

End of Charge Voltage

14.4V / 28.8V / 57.6V

Equalization

15.3V / 30.6V / 61.2V

Absorption Time:

2 Hours

6.1.2Auxiliary contact

Active in case of defect or manual turn off with the LED 10/11/12/13

6.2Reset value (default settings)

To come back to the default settings, press simultaneously on the push buttons 20/21 during at least 2 seconds. A beep will confirm the comeback to the factory settings. The inverter switches off after this operation. It can be turned on again after the beep.

6.3Battery voltages and absorption time

The voltage levels (low voltage, float charge, end of charge and equalization) and the duration of the absorption charge can be changed.

The display of these voltages and the times in the program mode are in accordance with the dia- gram shown below:

6.3.1Table of voltage and timing threshold

 

Low voltage

Float Charge

Absorption

 

Equalization

Absorpt. time

 

LED 13

 

LED 12

 

LED 11

 

LED 10

 

LED 10->13

LED

12V

24V

48V

12V

24V

48V

12V

24V

48V

12V

24V

48V

 

14

12.0

24.0

48.0

13.7

27.4

54.8

15.0

30.0

60.0

15.5

31.0

62.0

4 h

15

11.8

23.6

47.2

13.6

27.2

54.4

14.8

29.6

59.2

15.4

30.8

61.6

3 h

16

11.6

23.2

46.4

13.5

27.0

54.0

14.6

29.2

58.4

15.3

30.6

61.2

2 h

17

11.4

22.8

45.6

13.4

26.8

53.6

14.4

28.8

57.6

15.2

30.4

60.8

1 h

18

11.2

22.4

44.8

13.3

26.6

53.2

14.2

28.4

56.8

15.1

30.2

60.4

0 – 1Min.

The heavy printed values show the standard settings.

6.3.2Set the voltage and timing threshold

The programming is done in accordance with the following steps:

Push and hold down, the Push Button 21 (Program) and the Push Button 19 (Change status) for minimum 2 seconds simultaneously.

With the Push Button 20 (select) select with of the battery level and the absorption time to be changed.