3 Mounting and installing
3.1Installation place
The location of the
-Protection against unauthorized handling
-Dry dust free room, no condensation
-Never install directly over the battery and never in a cabinet together with the batteries
-Keep ventilation holes free. The ventilation of
only work efficiently when the appliance is fully lying on its back
In mobile installations it is important to keep down the vibrations as low as possible.
3.2Fixing
3.2.1XP-COMPACT
Basically the
3.3Protection cover IP23
This cover IP23 (Order ref.
3.4Connections
3.4.1General instructions on connecting
The cable connection on the terminals AC INPUT / AC OUTPUT / 16A 230VAC are carried out with a screwdriver Nr.1 and the connection on the SOLAR terminal with a screwdriver Nr.2.
The conductor cross section on the terminals AC INPUT / AC OUTPUT / 16A 230VAC of the con- necting cable must be minimum 2.5mm2.
All connecting cables and also the mounted battery cables must be fixed with strain relief clamps. The
The battery cables must never be extended. If the extension can not be avoided, then the conduc- tor cross section must be elevated accordingly.
To protect the battery cable, a fuse corresponding to the conductor cross section must be fixed directly on to the battery.
All cables must be tightly screwed in place. For safety, a yearly control is recommended. In mobile installations control must be carried out more often.