Studer Innotec XPC 2200-24 The Solar charge controller option, Set the transfer voltage threshold

Models: XPC 2200-24

1 23
Download 23 pages 51.43 Kb
Page 16
Image 16
4.8.1Set the transfer voltage threshold

STUDER Innotec

XP-COMPACT

 

 

the transfer contact is active, then you have at the output AC OUT the same voltage as that at the input. This voltage can not be modified by the XP-COMPACT!

4.8.1Set the transfer voltage threshold

The voltage threshold of the transfer is factory settled at 200Vac. This value is acceptable in most application. However, this value can be adjusted fro 150 to 230Vac if necessary. To proceed to the adjustment of this level, insert a screw-driver N° 0 vertically in the hole (23) and turn gently clock- wise or counter clockwise to increase or diminish the threshold level.. When the Input voltages reach the settled value on turning knob, the inverter switch off and the AC INPUT go directly on the AC OUTPUT. When the voltage INPUT is less of 20V the value set, the transfer is stop and the OUTPUT switch back on the inverter.

Don’t use the turning knobs “TRANSFERT” (23) to adjust the AC OUTPUT voltage! This is only it’s only a voltage threshold level to enable or disable the transfer.

4.8.2FAST (UPS)- MODE for the Transfer Switch

The quick and break free Transfer mode is programmed with a slide switch „Transfer Delay“ OFF, which is on the front side (cable connections side).

The aim of the XP-COMPACT is to supply the consuming appliance with a break-free alternating voltage. When the incoming voltage AC IN no longer matches values which have been set with the Turning Knob 23, the Inverter switches on at once. The transfer is carried out in 0.02 seconds. This quick transfer ensures a break-free function for most consuming appliances. If you have an alter- nating voltage back at the input AC IN, transfer system starts up again without any break, and the inverter is stopped.

4.8.3Delayed mode of the Transfer System

The delayed mode of the transfer system „Transfer Delay ON“ is programmed with the slide switch on front with the cable connections. The XP-COMPACT provides a break-free alternating voltage for the consuming appliance. A quick transfer switch is not always sensible nor is it always desired. For example, when the consuming appliances are operated by a small back-up generator, an over- load of a short duration on such a generator, i.e. start of a vacuum cleaner etc., has the effect of decreasing the voltage for a short time. As in such cases the transfer to the Inverter is not desir- able, the transfer system can be programmed with a delay. When the slide switch (Transfer delay) is in the „On“ position, the transfer to the inverter takes place with a delay of 5 seconds. If the volt- age falls below 100Vac, the transfer takes place without delay! The transfer switching to the In- verter takes place without any break.

4.9The Solar charge controller (option)

The XP-COMPACT also has a Solar Charge Controller built in. For charging the batteries, Solar modules can be connected to the screw terminal SOLAR +/-. The in-built controller is a „Shunt con- troller“ for the maximum input current of 30A for XPC 1400-12 and XPC 2200-24 and 20A for XPC 2200-48. The operating voltage of Solar panels to be connected must match the actual operating voltage of the XP-COMPACT and never exceeds the max. rated value.

Under no circumstances should any other systems such as wind-generator be connected at the input of the Solar Charge Controller.

The Solar Charge Controller works automatically and is always in operation. As soon as the energy is delivered from the Solar Charge Controller, LED 3 “SOLAR CHARGE” is lit and the batteries are being charged. The Solar Charge Controller works even when the Battery Charger is functioning. The way of working is the principally the same as that of the Battery Charger. The function is de- scribed in the section on Battery Charger. The programming and the adjustments, thanks the op- tional remote control, are carried out in accordance with the same conditions. Check with your bat- tery supplier which adjustments must be carried out for your battery.

User manual

XP-COMPACT V5.1 E

15

Page 16
Image 16
Studer Innotec XPC 2200-24 The Solar charge controller option, Set the transfer voltage threshold, STUDER Innotec