A-4 UltraEnterprise 6000/5000/4000 Systems ManualNovember 1996
A
A.3 Environmental Requirements
BTU rating 4680 BTU
Power factor 0.92 - 0.96
Plug type U.S. NEMA 5-15P
International 10A, single phase IEC 320,
connected for 220-240 Vac
TableA-9 CabinetServer Temperature,Humidity,
and Altitude Limits
Operating Nonoperating
Temperature 41°Fto95°F(5°Cto35°C)* -4°Fto 140°F (-20°Cto60°C)
Humidity 20% to 80% RH noncondensing,
27C max wb 93% RH
Altitude 9,843 ft (3 km) 39,370 ft (12 km)
*Maximum operating temperature is 95°F (35°C) when using tape media.
TableA-10 Standalone Server Temperature, Humidity,
and Altitude Limits
Operating Nonoperating
Temperature 41°Fto104°F(5°Cto40°C)* -4°F to 140°F (-20°Cto60°C)
Humidity 20% to 80% RH noncondensing,
27C max wb 93% RH
Altitude 9,843 ft (3 km) 39,370 ft (12 km)
*Maximum operating temperature is 95°F (35°C) when using tape media.
TableA-8 StandaloneServer Electrical Specifications (Continued)
Parameter Value