TOSHIBA
13)Additional warnings and notifications shall be posted at the equipment installation location as deemed required by Qualified Personnel.
CAUTION | When the UPS is in the Inverter mode, turning the breaker to the OFF |
position will cause the unit to go into the battery backup mode. The |
UPS will continue to provide power to the load. The unit must be in Bypass mode and then the breaker turned to the OFF position for the UPS to shut down power to the load.
CAUTION | Do not EPO (Emergency Power OFF) the UPS and then reset the |
breaker until the UPS has been fully discharged. The UPS could be | |
| damaged if the unit is not fully powered down before the breaker is |
| reset. |
4.0UPS Connections
4.1Power Connections
4.1.1Power Connections 15/25/30 kVA with Internal Batteries
The following illustrates the wiring connections from the power distribution panel (not part of the UPS) to the terminal block of the 15/25/30 kVA UPS Models
TB1
INPUT GROUND RESISTANCE
LESS THAN 10 OHMS
Optional Bypass Input:
*208 V requires
4200FA CT/XT User’s Manual | 20 |