Toshiba 4200FA CT/XT user manual Toshiba, 4200FA 30 kVA w/Internal Transformer

Models: 4200FA CT/XT

1 68
Download 68 pages 57.67 Kb
Page 35
Image 35
4200FA 30 kVA w/Internal Transformer

TOSHIBA

5.4

4200FA 30 kVA w/Internal Transformer

 

 

 

 

 

Model Number

T42#3*300#AMXN

 

 

Input

# =(B: 208; H: 220; C: 240; N: 380–415; D: 480; M: 600) VAC

 

 

Output

*=(F: 208; H: 220 wye; J: 240; P: 380–415 wye; K: 480 wye: M:600)

 

Rated Output Capacity

 

30 kVA

 

External Dimensions

20.0” x 36.3” x 59.7”

 

W x D x H (cm)

(50.8 cm x 92.2 cm x 151.6 cm)

Input

Rated Voltage

208; 220; 240; 380; 400; 415; 480; 600 VAC

 

(Determined by Input Transformer internal to the unit)

 

 

 

 

Voltage Variation

+10% to -30%; (-15% to -30%)

 

Rated Frequency

50/60 Hz

 

Input Cables Required

3 phase ; 3 Wire + GND

 

Dual Input Option Cables required

3 phase ; 4 Wire + GND

 

* Power Factor

Greater than 0.98 when in inverter mode

 

Required Input kVA

30.5 kVA

 

Walk-in Function

From 20% to 100% over 5 seconds

 

Inrush Current

Less than 8 times the rated current under synchronous operation

 

Current Limit

115% maximum

 

* Harmonic Currents

Less than 3% THD

Battery

DC Nominal (Voltage Range)

288 VDC (216 to 332 VDC)

 

Float Charge (Regulation)

324.0 VDC (± 2%)

 

Ripple Voltage

0.5 V R.M.S.

 

**Rated Back-up Time

Refer to Battery System Manual

 

Rated Charge Current

10.0 Amps

Output

Rated Voltage

(Determined by Output Transformer internal to the unit)

 

Rated Current

VA / Nominal Output Voltage / 1.73

 

Rated Power Factor

0.8 lagging

 

Output Cables Required

3 phase ; 4 Wire + GND

 

Voltage Regulation (phase-phase)

± 5% (0-100% balanced load);

 

± 6% (0-100% unbalanced load)

 

 

 

 

Voltage Adjustment Range

± 5V Manually from key pad

 

Phase Displacement

± 2° (0–100% balanced load);

 

± 4° (unbalanced load)

 

 

 

 

Rated Frequency

50 / 60 Hz

 

Frequency Regulation

± 0.1% in free running mode

 

Frequency Synchronous

± 0.5/1.0/1.5 Hz (± 1.0 Hz. std.)

 

switch selectable by qualified technician

 

 

 

 

Frequency Slew Rate

1 Hz/s to 3Hz/s (in 0.5 Hz steps)

 

Voltage Transients

± 5% (100% load step change);

 

± 3% (loss or return of input voltage);

 

(Recovery time: 50 ms)

 

± 8% (transfer of bypass to inverter)

 

 

 

 

Inverter Overload Capacity

125% 90 sec; 150% 30 sec

 

Bypass Overload Capacity

1000% 10ms; 125% 10 min.

 

Crest Factor

2.5–3.0 within the kW range

 

Neutral Line Conductor

1.73 (200%) times line rating

 

Harmonic Voltage Distortion

1.5% max (linear load)

 

Inrush Current protection

Automatic Transfer to bypass, then retransfer to inverter

 

 

 

Environment

Efficiency (Typical)

AC/DC/AC: 77%; DC/AC: 83%

 

Heat loss to be removed

23,216 BTU/hr (5,849 kcal/hr)

 

Audible Noise

60dB (A) at 1 meter from the front of the unit

 

Operating Temperature

32°–104°F (0°–40°C); optimal temperature is 77° F (25° C)

 

Operating Humidity

30–90% RH (non condensing)

 

Altitude ***

Less than 2000 meters

Items marked with an (*) are specified at rated conditions under balanced linear loads.

(**)Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site, and an initial charge time of 24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation.

(***) At 6600-ft (2000 m) above sea level, output capacity should be derated by 3% (Consult Factory for higher elevations).