TOSHIBA
5.0Specifications
5.14200FA 15 / 25 kVA @ 208 VAC Input/ 208 VAC Output w/Internal Batteries
| Model Number | C42F3F150XAMBN | C42F3F250XAMBN | |
| C42F3F150##MBN | C42F3F250##MBN | ||
|
| |||
| Rated Output Capacity | 15 kVA | 25 kVA | |
| External Dimensions | 20.0” x 36.3” x 59.7” | ||
| W x D x H (cm) | (50.8 cm x 92.2 cm x 151.6 cm) | ||
Input | Rated Voltage | 208 VAC | ||
| Voltage Variation | +10% to | ||
| Rated Frequency | 50 / 60 Hz | ||
| Input Cables required | 3 phase ; 4 Wire + GND | ||
| Dual Input Option Cables required | 3 phase ; 4 Wire + GND | ||
| * Power Factor | Greater than 0.98 when in inverter mode | ||
| Required Input kVA | 15 kVA |
| 24 kVA |
| From 20% to 100% |
| over 5 seconds | |
| Inrush Current | Less than 8 times the rated current under synchronous operation | ||
| Current Limit | 115% maximum | ||
| * Harmonic Currents | Less than 8.5% |
| Less than 5.5% |
Battery | DC Nominal (Voltage Range) | 288 VDC (216 | to 332 VDC) | |
| Float Charge (Regulation) | 324.0 VDC (± 2%) | ||
| Ripple Voltage | 0.5 V R.M.S. | ||
| **Rated | 7 min at full load |
| 5 min at full load |
| Rated Charge Current | 4.0 | Amps | |
Output | Rated Voltage | 208 / 120 VAC | ||
| Rated Current | 42.0 Amps |
| 69.5 Amps |
| Rated Power Factor | 0.8 lagging | ||
| Output Cables Required | 3 phase ; 4 Wire + GND | ||
| Voltage Regulation | ± 2% | ||
| Voltage Adjustment Range | ± 5V Manually from the key pad | ||
| Phase Displacement | ± 2° | ||
| Rated Frequency | 50 / 60 Hz | ||
| Frequency Regulation | ± 0.1% in free running mode | ||
| Frequency Synchronous | ± 0.5/1.0/1.5 Hz (± 1.0 Hz. std.) | ||
| switch selectable by qualified technician | |||
|
| |||
| Frequency Slew Rate | 1 Hz/s to 3Hz/s (in 0.5 Hz steps) | ||
| Voltage Transients | ± 5% (100% load step change); | ||
| ± 3% (loss or return of input voltage); | |||
| (Recovery time: 50 ms) | |||
| ± 8% (transfer of bypass to inverter) | |||
|
| |||
| Inverter Overload Capacity | 125% 90 sec; 150% 30 sec | ||
| Bypass Overload Capacity | 1000% 10 ms; 125% 10 min. | ||
| Crest Factor | |||
| Neutral Line Conductor | 1.73 (200%) times line rating | ||
| Harmonic Voltage Distortion | 1.5% max (linear load) | ||
| Inrush Current protection | Automatic Transfer to bypass, then retransfer to inverter | ||
|
|
|
|
|
Environment | Efficiency (Typical) | AC/DC/AC: 82%; DC/AC: 86% |
| AC/DC/AC: 85%; DC/AC: 87% |
| Heat loss to be removed | 8,428 BTU/hr (2,124 kcal/hr) |
| 11,489 BTU/hr (2,895 kcal/hr) |
| Audible Noise | 60dB (A) at 1 meter from the front of the unit | ||
| Operating Temperature | 32 | ||
| Operating Humidity | |||
| Altitude *** | Less than 2000 meters |
Items marked with an (*) are specified at rated conditions under balanced linear loads.
(**)Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site, and an initial charge time of 24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation.
(***) At
4200FA CT/XT User’s Manual | 31 |