Toshiba 4200FA CT/XT user manual Specifications, 15 kVA, 25 kVA

Models: 4200FA CT/XT

1 68
Download 68 pages 57.67 Kb
Page 32
Image 32
5.0Specifications

TOSHIBA

5.0Specifications

5.14200FA 15 / 25 kVA @ 208 VAC Input/ 208 VAC Output w/Internal Batteries

 

Model Number

C42F3F150XAMBN

C42F3F250XAMBN

 

C42F3F150##MBN

C42F3F250##MBN

 

 

 

Rated Output Capacity

15 kVA

25 kVA

 

External Dimensions

20.0” x 36.3” x 59.7”

 

W x D x H (cm)

(50.8 cm x 92.2 cm x 151.6 cm)

Input

Rated Voltage

208 VAC

 

Voltage Variation

+10% to -30%; (-15% to -30%)

 

Rated Frequency

50 / 60 Hz

 

Input Cables required

3 phase ; 4 Wire + GND

 

Dual Input Option Cables required

3 phase ; 4 Wire + GND

 

* Power Factor

Greater than 0.98 when in inverter mode

 

Required Input kVA

15 kVA

 

24 kVA

 

Walk-in Function

From 20% to 100%

 

over 5 seconds

 

Inrush Current

Less than 8 times the rated current under synchronous operation

 

Current Limit

115% maximum

 

* Harmonic Currents

Less than 8.5%

 

Less than 5.5%

Battery

DC Nominal (Voltage Range)

288 VDC (216

to 332 VDC)

 

Float Charge (Regulation)

324.0 VDC (± 2%)

 

Ripple Voltage

0.5 V R.M.S.

 

**Rated Back-up Time

7 min at full load

 

5 min at full load

 

Rated Charge Current

4.0

Amps

Output

Rated Voltage

208 / 120 VAC

 

Rated Current

42.0 Amps

 

69.5 Amps

 

Rated Power Factor

0.8 lagging

 

Output Cables Required

3 phase ; 4 Wire + GND

 

Voltage Regulation (phase-phase)

± 2% (0-100% balanced load); ± 3% (0-100% unbalanced load)

 

Voltage Adjustment Range

± 5V Manually from the key pad

 

Phase Displacement

± 2° (0–100% balanced load); ± 4° (unbalanced load)

 

Rated Frequency

50 / 60 Hz

 

Frequency Regulation

± 0.1% in free running mode

 

Frequency Synchronous

± 0.5/1.0/1.5 Hz (± 1.0 Hz. std.)

 

switch selectable by qualified technician

 

 

 

Frequency Slew Rate

1 Hz/s to 3Hz/s (in 0.5 Hz steps)

 

Voltage Transients

± 5% (100% load step change);

 

± 3% (loss or return of input voltage);

 

(Recovery time: 50 ms)

 

± 8% (transfer of bypass to inverter)

 

 

 

Inverter Overload Capacity

125% 90 sec; 150% 30 sec

 

Bypass Overload Capacity

1000% 10 ms; 125% 10 min.

 

Crest Factor

2.5–3.0 within the kW range

 

Neutral Line Conductor

1.73 (200%) times line rating

 

Harmonic Voltage Distortion

1.5% max (linear load)

 

Inrush Current protection

Automatic Transfer to bypass, then retransfer to inverter

 

 

 

 

 

Environment

Efficiency (Typical)

AC/DC/AC: 82%; DC/AC: 86%

 

AC/DC/AC: 85%; DC/AC: 87%

 

Heat loss to be removed

8,428 BTU/hr (2,124 kcal/hr)

 

11,489 BTU/hr (2,895 kcal/hr)

 

Audible Noise

60dB (A) at 1 meter from the front of the unit

 

Operating Temperature

32 –104 °F (0 – 40 °C); optimal temperature is 77 °F (25 °C)

 

Operating Humidity

30–90% RH (non condensing)

 

Altitude ***

Less than 2000 meters

Items marked with an (*) are specified at rated conditions under balanced linear loads.

(**)Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site, and an initial charge time of 24 hrs is necessary to obtain proper battery performance level before the unit is placed in operation.

(***) At 6600-ft (2000 m) above sea level, output capacity should be derated by 3% (Consult Factory for higher elevations).

4200FA CT/XT User’s Manual

31

Page 32
Image 32
Toshiba 4200FA CT/XT user manual Specifications, 15 kVA, 25 kVA