Image 38
6.0Operating the UPS

TOSHIBA

6.0Operating the UPS

6.1AC Input Mode (Normal Operation)

The following illustration shows circuit power flow when the UPS is operating normally in the AC Input Mode. The converter of the UPS, including a boost chopper circuit, converts the AC input power into DC power. The boost chopper circuit maintains a constant voltage and provides current limiting for charging the batteries. It also supplies a DC voltage of the proper level to the inverter section. The inverter section generates a high quality sine wave output voltage. The batteries are maintained in a constantly charged state when the UPS is in the “Normal Operation Mode.”

Power Flow

Input

Power

Isolating

XFMR

MBS

Bypass

MCCB

Converter

Charger/

Chopper

Inverter

Output Power

External

Batteries

Power flow in AC Input Mode

4200FA CT/XT User’s Manual

37

Page 38
Image 38
Toshiba 4200FA CT/XT user manual Operating the UPS, AC Input Mode Normal Operation, Power flow in AC Input Mode