6.7Battery Recharging
The illustration below shows a graphical representation of the UPS battery recharge process after a full discharge.
The recharge process usually consists of three steps. During the first step, the charging current is maintained at approximately 4.0 amperes for the 15/25/30 kVA with internal batteries, 10.0 amperes for the 15/25/30 kVA with internal transformer and approximately
11.5amperes for all 50 kVA models. This current is the maximum value that can be used to charge the batteries (for minimal recharge time) while assuring safety and long battery life. In the second step,
The following chart shows the rated maximum and minimum battery voltages, and the charge current for each of the sizes while the unit is maintained in a 75 °F (24 °C) ambient.
|
|
| Rated Battery Voltages |
|
| ||
| Model |
| 15/25/30 kVA |
| 50kVA | ||
|
| Internal | Internal | Internal |
| Internal | |
|
|
| Battery | Transformer | Battery |
| Transformer |
| V float | 324.0 VDC | 324 VDC |
| 324 | VDC | |
| V min | 216 VDC | 216 VDC |
| 216 VDC | ||
| I charge | 4.0 A | 10.0 A | 11.5 Amps |