Image 57
6.19.6Output Voltage Adjustment

TOSHIBA

6.19.6Output Voltage Adjustment

When the MENU key is pressed and held 3-4 seconds during normal 'AC Input Mode' of operation, the LCD screen displays the output voltage on the present output voltage adjust screen:

OUTPUT VOLT. ADJUST OUTPUT VOLTAGE.=###% >F1:DATA SET MODE

> Δ/:PREV/NEXT SCREEN

Press the F1 key to display the following active adjustment screen:

OUTPUT VOLT. ADJUST

REFERENCE ADJUST: ##

>Δ/:CHANGE DATA >ENTER: ACCEPT CHANGE

The locations marked ## will show the numerical value of the allowable voltage adjustment parameter values. Press the 'up' and 'down' arrow keys to adjust the setting from between

±5 volts. This will cause the unit's output voltage to adjust to within ±2% of its nominal value.

If the inverter is not running, and the output voltage cannot be adjusted; the following message will be displayed:

OUTPUT VOLT. ADJUST

ADJUST PROHIBITED

DATA CANNOT CHANGE >Δ/:PRV/NEXT SCREEN

Pressing the F1 key will have no effect on this display screen

6.19.7Equalize Charge Mode Select

Contact Toshiba Customer Support toll free at 1-877-867-8773 before using this option.

DAMAGE to the battery system may occur if this option is used improperly.