6.19.8Reset to Default Settings

TOSHIBA

6.19.8Reset to Default Settings

Press the MENU key to access the menu data screens and press the 'down' arrow key to scroll to the original factory 'default settings' adjustment screen display:

MENU DATA RESET DATA INITIALIZATION >F1: TO ACCESS RESET >Δ/:PRV/NEXT SCREEN

Press the F1 key to display the following active adjustment screen:

MENU DATA RESET

DATA INITIALIZATION

>MENU: NO DATA RESET >ENTER: ACCEPT CHANGE

When the ENTER key is pressed the following factory defaults are reset:

1)Resets the voltage-reference setting to +0

2)Resets the buzzer volume to 'loud'

3)Resets the serial station address to 31h

4)Resets the idle mode to 3 minutes

Press the MENU key to abandon the operation and return to the menu data screen.

6.20Overload Operation

When the UPS is operating and an overload condition is first detected, the following “Overload Warning” screen is displayed.

- UPS ON-LINE -

OUTPUT VOLTAGE= ###V

OUTPUT CURRENT= ###%

* UPS OL: REDUCE LOAD *

After a period of time, if the overload is still not reduced and the STOP/RUN key switch is in the RUN position, the UPS will automatically transfer to Bypass. If the overload condition is still present, the following screen will be displayed:

- BYPASS OPERATION - OUTPUT VOLTAGE=208 CURRENT= 114/116/114%

* UPS OL: REDUCE LOAD *

If the STOP/RUN key switch is in the STOP position; the UPS is in the Bypass Mode and, if the overload condition is still present, the following screen will be displayed:

- BYPASS OPERATION - OUTPUT VOLTAGE=208 CURRENT= 114/116/114%

* UPS OL: REDUCE LOAD *