4.1.3Recommended Wire Size and Torque Requirements UPS Input and Output Terminals
Minimum Wire Size and Torque Requirements
UPS Input and Output Terminals 15/25/30 kVA
(USE MINIMUM 75 °C INSULATED COPPER WIRING)
Phase: (A) (B) (C) | 15 kVA | 25 kVA |
| 30 kVA | |||
Input: (H1) (H2) (H3) | AWG | Torque | AWG | Torque | AWG |
| Torque |
208 V | 8 | 51 | 4 | 51 | 2 |
| 87 |
220 V | 8 | 51 | 4 | 51 | 2 |
| 87 |
240 V | 8 | 51 | 4 | 51 | 2 |
| 87 |
380 V | 10 | 35 | 8 | 51 | 6 |
| 51 |
400 V | 10 | 35 | 8 | 51 | 6 |
| 51 |
415 V | 10 | 35 | 8 | 51 | 6 |
| 51 |
480 V | 10 | 35 | 8 | 51 | 6 |
| 51 |
600 V | 10 | 35 | 10 | 35 | 10 |
| 35 |
All wire sizes are per the NEC. Maximum Wire Size is 2 AWG.
|
|
|
|
|
| 15 kVA |
|
|
|
| 25 kVA |
|
|
|
|
| 30 kVA |
|
| |||||||||
| Output: |
|
| AWG |
| AWG |
| Torque |
| AWG |
| AWG |
|
| Torque |
|
| AWG |
| AWG |
| Torque |
| |||||
|
|
| (L1)- |
|
|
| (L1)- |
|
|
|
|
| (L1)- |
|
|
| ||||||||||||
| (L1) (L2) (L3) (N) |
|
| (L3) |
| (N) |
| (N) |
| (L3) |
| (N) |
|
| (N) |
|
| (L3) |
| (N) |
| (N) |
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||
| 120/208 V | 8 | 4 |
| 51 | 51 | 4 | 2 |
|
| 51 |
| 87 |
| 2 | 2 |
| 87 |
| 87 |
| |||||||
| 127/220 V | 8 | 4 |
| 51 | 51 | 4 | 2 |
| 51 |
| 87 |
| 2 | 2 |
| 87 |
| 87 |
| ||||||||
| 240 V | 8 |
| N/A | 51 | N/A | 4 |
| N/A | 51 |
| N/A | 2 |
| N/A | 87 |
| N/A |
| |||||||||
| 220/380 V | 10 | 8 |
| 35 | 51 | 8 | 4 |
| 51 |
| 51 |
| 6 | 2 |
| 51 |
| 87 |
| ||||||||
| 230/400 V | 10 | 8 |
| 35 | 51 | 8 | 4 |
| 51 |
| 51 |
| 6 | 2 |
| 51 |
| 87 |
| ||||||||
| 240/415 V | 10 | 8 |
| 35 | 51 | 8 | 4 |
| 51 |
| 51 |
| 6 | 2 |
| 51 |
| 87 |
| ||||||||
| 277/480 V | 10 | 8 |
| 35 | 51 | 8 | 6 |
| 51 |
| 51 |
| 6 | 2 |
| 51 |
| 87 |
| ||||||||
| 600 V | 10 |
| N/A | 35 | N/A | 10 |
| N/A | 35 |
| N/A | 10 |
| N/A | 35 |
| N/A |
|
Neutral Conductors are rated @ 1.73 or 200% of phase conductors, per NEC. Maximum Wire Size is 2 AWG.
| Input/ Output (GND) |
|
| 15 kVA | 25 kVA | 30 kVA | |||
|
| AWG |
| Torque | AWG | Torque | AWG | Torque | |
| (G) | 10 |
| 35 | 8 | 51 | 6 | 51 |
Maximum Wire Size is 2 AWG.
Minimum Wire Size and Torque Requirements
UPS Optional Separate Bypass Input “TB4” 15 / 25kVA
(USE MINIMUM 75 °C INSULATED COPPER WIRING)
Phase: (A) (B) (C) | 15 kVA | 25 kVA |
| 30 kVA | |||
Input: (H1) (H2) (H3) | AWG | Torque | AWG | Torque | AWG |
| Torque |
208 V | 8 | 51 | 4 | 51 | 2 |
| 87 |
220 V | 8 | 51 | 4 | 51 | 2 |
| 87 |
240 V | 8 | 51 | 4 | 51 | 2 |
| 87 |
380 V | 10 | 35 | 8 | 51 | 6 |
| 51 |
400 V | 10 | 35 | 8 | 51 | 6 |
| 51 |
415 V | 10 | 35 | 8 | 51 | 6 |
| 51 |
480 V | 10 | 35 | 8 | 51 | 6 |
| 51 |
600 V | 10 | 35 | 10 | 35 | 10 |
| 35 |
Maximum Wire Size is 2 AWG.
4200FA CT/XT User’s Manual | 22 |