4.1.3Recommended Wire Size and Torque Requirements UPS Input and Output Terminals

Minimum Wire Size and Torque Requirements

UPS Input and Output Terminals 15/25/30 kVA

(USE MINIMUM 75 °C INSULATED COPPER WIRING)

Phase: (A) (B) (C)

15 kVA

25 kVA

 

30 kVA

Input: (H1) (H2) (H3)

AWG

Torque

AWG

Torque

AWG

 

Torque

208 V

8

51 in-lbs.

4

51 in-lbs.

2

 

87 in-lbs.

220 V

8

51 in-lbs.

4

51 in-lbs.

2

 

87 in-lbs.

240 V

8

51 in-lbs.

4

51 in-lbs.

2

 

87 in-lbs.

380 V

10

35 in-lbs.

8

51 in-lbs.

6

 

51 in-lbs.

400 V

10

35 in-lbs.

8

51 in-lbs.

6

 

51 in-lbs.

415 V

10

35 in-lbs.

8

51 in-lbs.

6

 

51 in-lbs.

480 V

10

35 in-lbs.

8

51 in-lbs.

6

 

51 in-lbs.

600 V

10

35 in-lbs.

10

35 in-lbs.

10

 

35 in-lbs.

All wire sizes are per the NEC. Maximum Wire Size is 2 AWG.

 

 

 

 

 

 

15 kVA

 

 

 

 

25 kVA

 

 

 

 

 

30 kVA

 

 

 

Output:

 

 

AWG

 

AWG

 

Torque

 

AWG

 

AWG

 

 

Torque

 

 

AWG

 

AWG

 

Torque

 

 

 

 

(L1)-

 

 

(inch-lbs.)

 

(L1)-

 

 

 

(inch-lbs.)

 

 

(L1)-

 

 

(inch-lbs.)

 

 

(L1) (L2) (L3) (N)

 

 

(L3)

 

(N)

 

(L1)-(L3)

(N)

 

(L3)

 

(N)

 

 

(L1)-(L3)

(N)

 

 

(L3)

 

(N)

 

(L1)-(L3)

(N)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120/208 V

8

4

 

51

51

4

2

 

 

51

 

87

 

2

2

 

87

 

87

 

 

127/220 V

8

4

 

51

51

4

2

 

51

 

87

 

2

2

 

87

 

87

 

 

240 V

8

 

N/A

51

N/A

4

 

N/A

51

 

N/A

2

 

N/A

87

 

N/A

 

 

220/380 V

10

8

 

35

51

8

4

 

51

 

51

 

6

2

 

51

 

87

 

 

230/400 V

10

8

 

35

51

8

4

 

51

 

51

 

6

2

 

51

 

87

 

 

240/415 V

10

8

 

35

51

8

4

 

51

 

51

 

6

2

 

51

 

87

 

 

277/480 V

10

8

 

35

51

8

6

 

51

 

51

 

6

2

 

51

 

87

 

 

600 V

10

 

N/A

35

N/A

10

 

N/A

35

 

N/A

10

 

N/A

35

 

N/A

 

Neutral Conductors are rated @ 1.73 or 200% of phase conductors, per NEC. Maximum Wire Size is 2 AWG.

 

Input/ Output (GND)

 

 

15 kVA

25 kVA

30 kVA

 

 

AWG

 

Torque

AWG

Torque

AWG

Torque

 

(G)

10

 

35 in-lbs.

8

51 in-lbs.

6

51 in-lbs.

Maximum Wire Size is 2 AWG.

Minimum Wire Size and Torque Requirements

UPS Optional Separate Bypass Input “TB4” 15 / 25kVA

(USE MINIMUM 75 °C INSULATED COPPER WIRING)

Phase: (A) (B) (C)

15 kVA

25 kVA

 

30 kVA

Input: (H1) (H2) (H3)

AWG

Torque

AWG

Torque

AWG

 

Torque

208 V

8

51 in-lbs.

4

51 in-lbs.

2

 

87 in-lbs.

220 V

8

51 in-lbs.

4

51 in-lbs.

2

 

87 in-lbs.

240 V

8

51 in-lbs.

4

51 in-lbs.

2

 

87 in-lbs.

380 V

10

35 in-lbs.

8

51 in-lbs.

6

 

51 in-lbs.

400 V

10

35 in-lbs.

8

51 in-lbs.

6

 

51 in-lbs.

415 V

10

35 in-lbs.

8

51 in-lbs.

6

 

51 in-lbs.

480 V

10

35 in-lbs.

8

51 in-lbs.

6

 

51 in-lbs.

600 V

10

35 in-lbs.

10

35 in-lbs.

10

 

35 in-lbs.

Maximum Wire Size is 2 AWG.