TOSHIBA
4.5.2RS-232C
The
| Input Voltage | Output Voltage |
Operating Conditions | Input Frequency | Output Frequency |
| Battery Voltage | Output Current |
|
|
|
| Utility Power OK |
|
| Low Battery Voltage Detected | |
UPS Operating Status | UPS in BYPASS Mode |
|
(Described as “yes or “no”) | UPS in NORMAL Mode |
|
| Input and Output Frequency Synchronized | |
| UPS FAULT Occurred |
|
| DC Bus |
|
| DC Bus |
|
| DC Bus |
|
Fault Details | Input |
|
Overheat |
| |
(Described as “occurred” or “not occurred”) |
| |
Overload Being Timed |
| |
|
| |
| Overload (allowable time exceeded) | |
| Output | |
| Output |
The connector pin assignment and female connector outline are illustrated below.
Pin | I/O | Symbol | Description | DB9 Female connector outline | ||||
1 |
| This pin is not used |
| (facing connector) |
| |||
2 | Input | RXD | Receive Data | 5 | 4 | 3 | 2 | 1 |
|
|
|
| |||||
3 | Output | TXD | Transmit Data | |||||
|
|
|
|
|
|
|
|
|
4 | Output | DTR | Data Terminal Ready |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
5 | - | SG | Signal Ground |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
6 | Input | DSR | Data Set Ready |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
7 | Output | RTS | Request To Send | 9 |
| 8 | 7 | 6 |
8 | Input | CTS | Clear To Send |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
9 |
| This pin is not used |
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
4.5.3UPS Shutdown (via RS-232C)
When the UPS is operating from its internal batteries, a 'shutdown' order can be sent to the UPS instructing it to turn OFF after a
4200FA CT/XT User’s Manual | 30 |