4.4Control Circuit and External Interface Connections 50 kVA

The following illustrates the wiring connections of the Control Circuits, and Battery Interface Circuits for the 50kVA.

 

 

(3)

Battery Shunt Trip

(15)

Low Battery

(4)

Battery Shunt Trip

(5)

Battery Aux.

(16)

Battery Discharge

(6) Battery Aux.

(17)

Fault

 

 

(18)Not Used

(19)Inverter Supply

(20)Inverter Supply

(21)P24A3

(22)Remote Run

(23)P24A3

(24)Remote Stop

(25)Bypass

(26)COMMON

(27)EPO

(28)EPO

4.4.1Recommended Wire Size and Torque Requirements UPS Control and Battery Interface 50 kVA

Minimum Wire Size and Torque Requirements

UPS Control and Battery Interface Circuits

USE MINIMUM 75 °C COPPER WIRING

TERMINAL

 

50 kVA

 

 

TIGHTENING

(TERMINAL #)

AWG

 

 

TORQUE

 

 

UPS CONTROL CIRCUITS

14-16

 

8 in-lbs.

(1-24)*

 

 

 

 

BATTERY CONTROL

14-16

 

8 in-lbs.

CIRCUITS (3-6)*

 

 

 

 

*Indicates Class 1 wiring methods are to be used. Maximum Wire Size is 12 AWG.

4200FA CT/XT User’s Manual

28