4.4Control Circuit and External Interface Connections 50 kVA
The following illustrates the wiring connections of the Control Circuits, and Battery Interface Circuits for the 50kVA.
|
| (3) | Battery Shunt Trip | |
(15) | Low Battery | (4) | Battery Shunt Trip | |
(5) | Battery Aux. | |||
(16) | Battery Discharge | |||
(6) Battery Aux. | ||||
(17) | Fault | |||
|
|
(18)Not Used
(19)Inverter Supply
(20)Inverter Supply
(21)P24A3
(22)Remote Run
(23)P24A3
(24)Remote Stop
(25)Bypass
(26)COMMON
(27)EPO
(28)EPO
4.4.1Recommended Wire Size and Torque Requirements UPS Control and Battery Interface 50 kVA
Minimum Wire Size and Torque Requirements
UPS Control and Battery Interface Circuits
USE MINIMUM 75 °C COPPER WIRING
TERMINAL |
| 50 kVA | |
|
| TIGHTENING | |
(TERMINAL #) | AWG |
| |
| TORQUE | ||
|
| ||
UPS CONTROL CIRCUITS |
| 8 | |
| |||
|
|
| |
BATTERY CONTROL |
| 8 | |
CIRCUITS |
| ||
|
|
|
*Indicates Class 1 wiring methods are to be used. Maximum Wire Size is 12 AWG.
4200FA CT/XT User’s Manual | 28 |