E6581281 f
- 7 -
2.5. Communications-related parameters
In a network, VF-AS1/PS1 (DEV002Z) serves as a DeviceNet slave device. The
DEV002Z configuration is set by the following parameters.
The supported parameters for each drive and their allowable adjustment ranges are
defined in the appropriate Electronic Data Sheet (EDS) files. EDS files can be downloaded
via the internet from
http://www.inverter.co.jp/product/inv/vfas1/dev/index_i.htm
Parameter Function Adjustment range Default setting
f830 *Communication option
setting 1
Assembly
Object
0: Instance 20/70
1: Instance 21/71
2: Instance 100/150
3: Instance 101/151
4: Instance 102/152
0
f831
-
f846
Communication option
setting 2 - 13
Refer to section 3.4.5.6. -
f851 Inverter operation at the
communications
loss action
(Network wire breaks)
0: Stop and Communication release
1: None
2: Deceleration stop
3: Coast stop
4: Emergency stop
5: Preset speed operation command
(Operating at the preset speed operation
frequency set with f852)
0
f852 Preset speed operation
selection
0: None
1 to 15:Preset speed
0
f853 Monitoring of
communication device
station address
Displays the MAC ID number assigned using the DIP
switch.
0 to 63
1
f854 Monitoring of
communications
device’s baud rate
Displays the network communication speed set
with the DIP switch.
0: 125kbps
1: 250kbps
2: 500kbps
0
f899 Network option
reset setting
0: None
1: Resetting the DEV002Z and the inverter
0
* When the parameter is changed, the power must be cycled (or set f899 to 1) to the
VF-AS1/PS1 for the changes to take effect.
** When fmod or cmod is set to “Communication Input”, VF-AS1/PS1 drives without
Net Ref (Frequency link) or Net Ctrl (command link) at each Instance.