INDOOR UNIT CONTROL CIRCUIT (Continued)
NO. | Item |
| Overview of specifications | Remarks |
12 | HA control | (1) | When connected to a remote control system | A connector (separately |
|
|
| remote on/off interface), operation ON/OFF can be controlled by | available) is required |
|
|
| the HA signal input. | when using the HA |
|
| (2) | Outputs operation ON/OFF status to the HA output terminal. | terminal CH61 for remote |
|
| (3) | HA signal input/output specifications conform to the JEMA | ON/OFF control. |
|
|
| standard. |
|
|
|
|
| When group operation is |
|
|
|
| in use, connect the |
|
|
|
| connector to either header |
|
|
|
| or follower indoor unit. |
|
|
|
|
|
13 | Filter sign | (1) | Transmits filter replacement signal to remote controller for | “FILTER” lamp ON |
| indication |
| indication on the LCD when accumulated operation hours of |
|
| (unavailable for |
| indoor unit fan exceeds the specified time (150 hours). |
|
| wireless type) |
|
|
|
|
| (2) | Clears accumulation timer upon receiving the filter reset signal |
|
|
|
| from remote controller. At this time, when the specified time has |
|
|
|
| already passed, the accumulated time is reset and the filter sign |
|
|
|
| disappears from the LCD. |
|
|
|
|
|
|