Troubleshooting (Continued)
3. Troubleshooting for Each Check CodeCheck code | Check code name | Possible causes |
|
|
|
[E01] | I/U - R/C communication error | AImproper R/C wire connection |
(New code) | (detected by R/C) | BFailure of I/U power supply |
|
| CFailure of I/U board |
|
| DInvalid R/C address setting |
|
| EFailure of R/C board |
|
|
|
Are R/C wires | NO |
A/B correct? |
|
YES |
|
Improper harness
YES
connection from I/U terminal block?
NO |
|
Group control | NO |
operation? |
|
YES |
|
Are all indoor | NO |
units powered ON? |
|
YES |
|
Is R/C powered ON?A/B | NO |
terminals: Approx. 18VDC |
|
YES |
|
Is “no header” | YES |
set by double R/C? |
|
NO |
|
Correct R/C wires.
Correct connector connection.
Check circuit wiring.
Check I/U power connection (power off and on).
Check I/U boards.
→Replace defective board.
Correct one header/one follower. (R/C address connector)
Check R/C board.
→Replace it if necessary.