Troubleshooting (Continued)
Check code | Check code name | Possible causes |
|
|
|
[E04] | I/U - O/U communication error | AImproper connector connection between I/U and O/U |
(New code) | (detected by I/U) | BImproper wire connection between I/U and O/U |
|
| CFailure of I/U or O/U board |
|
| DCase thermo sensor ON |
|
| EInvalid I/U board switch setting |
|
|
|
NO
Does O/U work?
YES
Check I/U boards.
→Replace defective board.
Is group address set correctly? | NO | ||
| |||
YES |
|
| |
Are 1/2/3 wires normal? | NO | ||
| |||
YES |
|
| |
Are connectors from I/U and | NO | ||
| |||
O/U connected normally? |
| ||
YES |
|
| |
Is I/U switch SW02 |
| NO | |
setting correct? Bit 1, 2: OFF |
| ||
YES |
|
| |
Does voltage between | NO | ||
I/U terminal 2 and 3 fluctuate? |
| ||
|
| ||
* Measure within | |||
YES | 20 seconds | ||
from power on. | |||
Is 280VDC | |||
| NO | ||
applied across IPDU main | |||
| |||
circuit capacitor? |
|
| |
YES |
|
| |
Is 280VDC supplied to | NO | ||
| |||
CDB? (CN03) |
|
| |
YES |
|
| |
Is 7VDC supplied |
| NO | |
to CDB? Is | |||
| |||
connection normal? |
|
| |
YES |
|
| |
Is case thermo sensor | NO | ||
| |||
connected? (CN500) |
|
| |
YES |
|
| |
Is case thermo sensor working? | NO | ||
|
YES
Check and correct refrigerant volume.
Check code “14”.
Correct wires.
Correct connector connection.
Correct switch setting on
Check
→Replace it if necessary.
Black C
White B
A
Terminal block
Replace IPDU.
Replace IPDU.
Replace IPDU.
Correct connector connection.
Correct connector connection.
Check
→Replace it if necessary. Check CDB. → Replace it if
necessary.