Check code | Check code name | Possible causes |
|
|
|
[C05], [C06] | ||
(Central controller) | communication error |
|
|
|
|
Is I/U
powered ON?
YES
Is harness from I/U
terminal block
connected properly?
YES
Can I/U be
operated by R/C
individually?
YES
Are U3/U4 com. cables. normal?
*1
YES
When a unit
connected to U3/U4
is in a group, is it set to header unit?
YES
Free from noise?
YES
Can other units
controlled by
central R/C? Is I/U
operating status
reflected?
YES
Is the code [C05]?
NO
Is I/U onboard fuse
F03 normal?
YES
NO
NO
NO
NO
*Check wrong connection, disconnection, and shield wire’s contact with com. cable.
NO
NO
NO
YES
NO
Power ON.
Correct connector connection.
Correct com. cable.
Set the connected unit to header unit.
Remove noise source.
Check central controller.
→Replace it if necessary.
Confirm normal connection of com. cable. Change connector connection CN40 to CN44 (EMG) on I/U board.
Check I/U boards. → Replace
defective board.
– 48 –