Check code

 

Check code name

Possible causes

 

 

 

[L20]

Duplication of central control address

Central control address is duplicated.

(New code)

 

 

 

 

 

 

 

Are U3/U4

 

NO

 

communication

 

cables connected

Correct cable connection.

 

normally?

 

 

YES

 

 

 

 

 

 

When a unit

connected to U3/U4 NO is in a group, is it set

to header unit?

YES

Check and correct I/U address, central control address.

Set the connected unit to header unit.

 

Check code

 

Check code name

Possible causes

 

 

 

 

 

 

 

[L30]

 

I/U external interlock

When an external alarm is input

 

(New code)

 

 

 

 

 

 

 

 

 

 

 

Is external device

NO

 

 

 

 

Check I/U boards.

 

connected to CN80?

 

 

Replace defective board.

 

YES

 

 

 

 

 

 

 

 

 

NO

 

 

 

Is external device

 

Check external device.

 

working normally?

 

 

Replace it if necessary.

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

Check possible error

 

 

 

 

causes.

 

 

 

 

 

 

 

 

 

44