Check code | Check code name | Possible causes |
|
|
|
[E09] | Duplication of R/C header | R/C header setting is duplicated. |
(New code) |
|
|
|
|
|
Are 2 headers set | YES |
by double R/C? |
|
NO |
|
Correct one header/one follower. (R/C address connector)
Check R/C board.
→Replace it if necessary.
Check code | Check code name | Possible causes |
|
|
|
[E18] | Communication error between header | A Improper wire connection between I/U |
(New code) | and follower I/U | B Improper wire connection between I/U and O/U |
|
| C Failure of I/U board |
|
| D Invalid I/U board switch setting |
|
|
|
Are A/B wires | NO |
normal? |
|
YES |
|
Improper harness | YES |
connection from I/U terminal |
|
block? |
|
NO |
|
Is I/U switch SW02 | NO |
setting correct? |
|
Bit 1, 2: OFF |
|
YES |
|
Group control operation? | NO |
| |
YES |
|
Are all indoor | NO |
units powered ON? |
|
YES |
|
| NO |
Twin or triple control? |
|
YES |
|
Improper signal | YES |
connection between I/U |
|
and O/U? |
|
NO |
|
Correct R/C wire connection.
Correct connector connection.
Check circuit wiring.
Correct switch setting on
Check I/U power connection (power off and on).
Correct signal wire connection between I/U and O/U.
Check
→Replace it if necessary.
– 40 –