Replace ignition

No

 

 

module.

 

 

 

Turn up thermostat.

 

Place a jumper across

 

No

the thermostat terminals. No

Does the fan turn on?

 

Does the fan turn on?

 

 

 

 

Yes

Check thermostat wiring and replace thermostat if necessary.

Yes

Is there power out

from pin 10 on

ignition module?

Yes

Is there power (230V)

at the burner?

No

Check relay wiring

(if applicable) and wiring

to the burner.

Yes

Remove electrical plug

from the pressure switch; place jumper between black & white leads. Does the fan turn on?

Yes

Replace pressure switch.

Remove obstruction.

Replace Fan.

Yes

Unplug burner.

No Does the fan turn freely?

No

Yes

Is the fan obstructed?

No

Fan bearings may have failed. Replace fan.

16.1 Troubleshooting Flow Chart (Linear, Double Linear

Is there spark at the

Unplug burner and check

Is the igniter gap

No electrode and ignition wire. No

set at 3 mm?

igniter?

Are they damaged?

 

 

Yes

No

 

Replace electrode and

Carefully reset gap

 

ignition wire as needed.

to 3 mm.

 

 

Replace automatic

 

 

control unit.

63 of 73

 

Is the flue pipe or

 

Yes

the inlet of the

Yes

 

burner obstructed?

 

 

No

 

Are the hoses to the pressure No switch secure and leak free?

Yes

Remove electrical plug No from the pressure switch;

place jumper between black & white leads. Does the fan turn on?

Yes

Replace pressure switch.

Remove obstruction.

Repair, replace or

tighten hoses as necessary.