Roberts Gorden HE50UT, HE20ST, HE50DL and U-Tube, Troubleshooting Flow Chart Linear, Double Linear

Models: HE35UT HE45UT HE40ST HE50DL HE25ST HE50UT HE20ST HE70DL HE30ST HE25UT HE15UT HE40DL HE35ST HE60DL HE15ST HE40UT HE20UT HE50ST HE45ST HE30UT HE30DL

1 82
Download 82 pages 30.77 Kb
Page 69
Image 69

 

 

Replace ignition

No

 

 

module.

 

 

 

Turn up thermostat.

 

Place a jumper across

 

No

the thermostat terminals. No

Does the fan turn on?

 

Does the fan turn on?

 

 

 

 

Yes

Check thermostat wiring and replace thermostat if necessary.

Yes

Is there power out

from pin 10 on

ignition module?

Yes

Is there power (230V)

at the burner?

No

Check relay wiring

(if applicable) and wiring

to the burner.

Yes

Remove electrical plug

from the pressure switch; place jumper between black & white leads. Does the fan turn on?

Yes

Replace pressure switch.

Remove obstruction.

Replace Fan.

Yes

Unplug burner.

No Does the fan turn freely?

No

Yes

Is the fan obstructed?

No

Fan bearings may have failed. Replace fan.

16.1 Troubleshooting Flow Chart (Linear, Double Linear

Is there spark at the

Unplug burner and check

Is the igniter gap

No electrode and ignition wire. No

set at 3 mm?

igniter?

Are they damaged?

 

 

Yes

No

 

Replace electrode and

Carefully reset gap

 

ignition wire as needed.

to 3 mm.

 

 

Replace automatic

 

 

control unit.

63 of 73

 

Is the flue pipe or

 

Yes

the inlet of the

Yes

 

burner obstructed?

 

 

No

 

Are the hoses to the pressure No switch secure and leak free?

Yes

Remove electrical plug No from the pressure switch;

place jumper between black & white leads. Does the fan turn on?

Yes

Replace pressure switch.

Remove obstruction.

Repair, replace or

tighten hoses as necessary.

and U-Tube)

SECTION 16: TROUBLESHOOTING

Page 69
Image 69
Roberts Gorden HE50UT, HE20ST, HE50DL, HE45UT, HE30DL, HE50ST and U-Tube, Troubleshooting Flow Chart Linear, Double Linear