Roberts Gorden HE15ST Undershield, HE30DL, HE20ST, HE40DL, HE25ST, HE50DL, HE30ST, HE60DL, HE35ST

Models: HE35UT HE45UT HE40ST HE50DL HE25ST HE50UT HE20ST HE70DL HE30ST HE25UT HE15UT HE40DL HE35ST HE60DL HE15ST HE40UT HE20UT HE50ST HE45ST HE30UT HE30DL

1 82
Download 82 pages 30.77 Kb
Page 13
Image 13

SECTION 3: CLEARANCES TO COMBUSTIBLES

NOTE: 1. All dimensions are from the surfaces of all tubes, couplings, tees, elbows and crosses.

2.Clearances B, C and D can be reduced by 50% after 7500 mm of tubing downstream from the burner.

3.All measurements are in millimeters.

FIGURE 7: LINEAR & DOUBLE LINEAR, 2 FOOT DECO GRILLE, PROTECTIVE GRILLE

 

A

Model

HE15ST HE30DL

HE20ST HE40DL

HE25ST HE50DL

HE30ST HE60DL

HE35ST HE70DL

HE40ST

HE45ST

HE50ST

 

 

A

150

150

150

150

150

150

200

200

C

B

890

970

970

1020

1170

1220

1280

1330

B

D

 

 

 

 

 

 

 

 

 

C

1570

1650

1650

1780

1930

1970

2010

2080

 

D

890

970

970

1020

1170

1220

1280

1330

FIGURE 8: UNDERSHIELD **

A

 

 

Model

 

 

 

A

C

B

D

B

 

 

 

 

 

C

D

** When installed in the first 3 m.

HE15ST

HE30DL

150

990

840

990

HE20ST

HE40DL

150

1020

965

1020

HE25ST

HE50DL

150

1270

1120

1270

HE30ST

HE60DL

150

1270

1120

1270

HE35ST

HE70DL

150

1370

1220

1370

HE40ST

150

1400

1270

1400

HE45ST

-

-

-

-

HE50ST

-

-

-

-

FIGURE 9: LINEAR & DOUBLE LINEAR, VENTING

 

E

Radiant tubes

Fan

F

Model

E

F

HE15ST

HE30DL

1000

500

HE20ST

HE40DL

1000

500

HE25ST

HE50DL

1000

500

HE30ST

HE60DL

1000

500

HE35ST

HE70DL

1000

500

HE40ST

1000

500

HE45ST

1000

500

HE50ST

1000

500

7 of 73

Page 13
Image 13
Roberts Gorden HE15ST Undershield, HE30DL, HE20ST, HE40DL, HE25ST, HE50DL, HE30ST, HE60DL, HE35ST, HE70DL, Model, HE40ST