Roberts Gorden HE50ST Vent Pipe, Outside Air Inlet, Tubes, Gas Line, Burner Observation, Window

Models: HE35UT HE45UT HE40ST HE50DL HE25ST HE50UT HE20ST HE70DL HE30ST HE25UT HE15UT HE40DL HE35ST HE60DL HE15ST HE40UT HE20UT HE50ST HE45ST HE30UT HE30DL

1 82
Download 82 pages 30.77 Kb
Page 67
Image 67

 

SECTION 15: SERVICING INSTRUCTIONS

 

 

 

Vent Pipe

Venting must be intact. Using a flashlight, look for obstructions, cracks on the pipe,

 

gaps in the sealed areas or corrosion.

 

The area must be free of dirt and dust.

 

Remove any carbon deposits or scale using a wire brush.

 

See Page 49, Section 11.

 

 

 

Outside Air Inlet

Inlet must be intact. Look for obstructions, cracks on the pipe, gaps in the sealed

 

areas or corrosion.

 

The area must be free of dirt and dust. Clean and reinstall as required.

 

 

 

Tubes

Make sure there are no cracks.

 

Make sure tubes are connected and suspended securely.

 

See Page 11, Section 5.

 

Make sure there is no sagging, bending or distortion.

 

 

 

Gas Line

Check for gas leaks. See Page 52, Section 12.

 

 

 

Burner Observation

Make sure it is clean and free of cracks or holes.

Window

Clean and replace as required.

 

 

 

Blower Scroll, Wheel and

Compressed air or a vacuum cleaner may be used to clean dust and dirt.

Motor

 

 

 

 

 

Burner Cup and Orifice

Clear of obstructions (even spider webs will cause problems).

 

Carefully remove any dust and debris from the burner.

 

 

 

Electrode

Replace if there are cracked ceramics, excessive carbon residue, or erosion of the

 

electrode.

 

The electrode gap should be 3 mm.

 

 

 

Thermostat

There should be no exposed wire or damage to the thermostat.

 

See Page 54, Section 13.

 

 

 

Suspension Points

Make sure the heater is hanging securely.

 

Look for signs of wear on the chain or ceiling.

 

See Page 11, Section 5.

Sports Hall Guard,

Decorative and Protective

Grilles (optional)

The grille must be securely attached. If the grille is loose or off, contact a contractor qualified in the installation and service of gas-fired heating equipment for repair.

Check that side reflector extensions are installed correctly and secured in place if necessary. (Decorative grille only.)

See Page 44, Section 10.3.3 and Page 45, Section 10.4.

Make sure shield is installed correctly and secured in place if necessary. (Decorative grille only.) See Page 44, Section 10.3.2.

Wall Tag

If a wall tag is present, make sure it is legible and accurate. Please contact

 

Roberts-Gordon LLC or your ROBERTS GORDON® independent distributor if you

 

need a wall tag. See Page 4, Section 2.1.

 

 

61 of 73

Page 67
Image 67