Roberts Gorden HE25ST, HE20ST Individual Flue Connection Detail, Flue Connection Dimensions

Models: HE35UT HE45UT HE40ST HE50DL HE25ST HE50UT HE20ST HE70DL HE30ST HE25UT HE15UT HE40DL HE35ST HE60DL HE15ST HE40UT HE20UT HE50ST HE45ST HE30UT HE30DL

1 82
Download 82 pages 30.77 Kb
Page 56
Image 56

BLACKHEAT® HE INSTALLATION OPERATION AND SERVICE MANUAL

Figure 29: Individual Flue Connection Detail

 

Fan Assembly

Fan Tube

 

Nut

 

Lockwasher

Screw

(Torque: 2 Nm

Flue Adapter

18 in lb)

 

Flue Pipe

 

Figure 30: Flue Connection Dimensions

C

End of Tube

A

Fan Tube

Fan

B

Fan Model

A

B

C

MB 56 2B M

98 mm

105 mm

52 mm

Torin DSF-133-42

79 mm

95 mm

45 mm

Torin DSA-524-202

86 mm

102 mm

51 mm

Magnetek JF1G

89 mm

102 mm

51 mm

Fan Part Number

A

B

C

90710051 (IP55)

76 mm

95 mm

31 mm

90710052 (IP55)

82 mm

101 mm

38 mm

90710053 (IP55)

82 mm

101 mm

38 mm

11.6 Outside Combustion Air Supply

Clean air must be ducted into the burner box through the 100 mm diameter spigot on the back of the burner box.

See Page 49, Section 11.3 for recommendations on duct length. Air duct should be as straight as possible. Consult the manufacturer if more than 1 x 90° bend is necessary. The fresh air duct must be self supporting.

11.6.1 Air Supply Requirements

When fresh air duct is used, follow one of these rules:

The flue must penetrate the roof while fresh air can penetrate any wall. (See Page 51, Figure 31).

The flue and fresh air supply must penetrate the roof at a minimum of 1,000 mm apart.

(See Page 51, Figure 31).

The flue must penetrate 1,000 mm higher than the fresh air inlet on the same wall. (See Page 51, Figure 31).

50 of 73

Page 56
Image 56