SECTION 18: SPECIFICATIONS
SECTION 18: SPECIFICATIONS
18.1 Material Specifications
18.1.1 Combustion and Tubes
100 mm dia. 16 gauge heat treated aluminised mild steel.
18.1.2 Reflectors
NS3 H14 aluminium or 1.4016 2R stainless steel (option).
18.2 Heater Specifications
18.2.1 Sequence Controller
Fully automatic, single try, direct spark,
100% shut off ignition flame rectification module.
18.2.2 Electrical
Rating: 230 V, 50 Hz, 1 Ø, 1 A
Connection: minimum IP55 junction box
18.2.3 Gas Supply
Connection: Rc1/2 (1/2" BSP int)
Natural G20:
Minimum - Inlet 15 mbar (6 in wg)
Maximum - Inlet 50 mbar (20 in wg)
Natural G25:
Minimum - Inlet 17.5 mbar (7 in wg)
Maximum - Inlet 50 mbar (20 in wg)
LP Gas (Propane or Butane): Minimum - Inlet 32.5 mbar (13 in wg) Maximum - Inlet 50 mbar (20 in wg)
18.3 Venting Specifications
18.3.1 Fans
HE15, 20, 25, 30, 35 | Model: Torin DSF |
HE40, 45, 50 | Model: AO Smith JF1G |
HE30DL, 40DL | Model: Torin DSA |
HE50DL, 60DL,70DL | Model: Magnetek JF1G |
18.3.2 IP54 Protected Fans
HE15, 20, 25, 30, 35 | ........ Model: Torin DSA |
| (P/N 90710051) |
HE40, 45, 50 | Model: Torin DSF |
| (P/N 90710053) |
HE30DL, 40DL | Model: Torin DSA |
| (P/N 90710052) |
HE50DL - 70DL | Model: Torin DSF |
| (P/N 90710053) |
Multiburner | Model: Airflow 83 BTLW IP55 |
...................... | Model: Airflow 90 BTLW IP55 |
Consult the manufacturer for availability of alternate fans.
18.3.3 Flue
The flue must be 100 mm, or greater in diameter, and must conform to National Codes. The flue must be self supporting. Inlet must be 100 mm diameter.
Multiburner - Flue will be 150 mm diameter. Flue material must conform to National Codes. The flue must be self supporting.
18.4 Suspension Specifications
Hang heater with materials with a minimum working load of 33 kg.
18.5 Controls Specifications
Time switches, thermostats, etc. can be wired into the electrical supply. External controls supplied as an optional extra.
71 of 73