SECTION 15: SERVICING INSTRUCTIONS

SECTION 15: SERVICING INSTRUCTIONS

DANGER

 

WARNING

 

Electrical Shock Hazard

Explosion Hazard

Burn Hazard

Cut/Pinch Hazard

Disconnect electric

Turn off gas supply to

Allow heater to cool

Wear protective gear

heater before service.

before service.

during installation,

before service.

 

 

operation and service.

 

 

Tubing may still be hot

More than one

 

Edges are sharp.

disconnect switch may

 

after operation.

be required to

 

 

 

disconnect electric from

 

 

 

heater.

 

 

 

Heater must be

 

 

 

connected to a properly

 

 

 

grounded electrical

 

 

 

source.

 

 

 

Failure to follow these instructions can result in death, electric shock, injury or property damage.

IMPORTANT: Never use the heater as a support for ladders or other access equipment. Always test for gas soundness with a suitable detection fluid after completing any servicing or exchange of gas carrying component. On completion of any service/fault finding tasks which require the breaking and remaking of electrical connections, the checks:- A: Earth Continuity, B: Polarity and C: Resistance to Earth must then be repeated.

15.1.3 Tube and Reflector Maintenance

With burner and fan removed, clean the outer surfaces of the tubes using a brush and wipe the inner surface of the reflector with a soft damp cloth - use a household detergent if necessary. Never use abrasive cleaners on the reflectors. Reassemble the burner and fan in reverse order. Carry out the Testing Procedure. See Page 58, Section 14.2.

15.1 Annual Procedure

Carry out the following procedure annually. The preferred time would be immediately before the winter heating period. If very dirty conditions arise, it may be necessary to carry out this procedure more often. If the unit takes in air through an air duct or filter assembly, more frequent service may be necessary.

15.1.1 Burner and Fan Removal

Isolate the heater from the gas and electrical supplies. Remove the fan plug from the burner. Unscrew the securing screws on the burner flange. The burner can now be removed. Take care not to disturb the gasket on the flanged burner tube. Unscrew the securing screw on the fan flange spigot. The fan can now be removed.

15.2 Sealing Gaskets

During annual service, all gaskets, as indicated on Page 68, Section 17, must be inspected for cuts, misalignment or dryness. All round rubber gaskets, sealing the screw holes, must be replaced in three year intervals or earlier as needed. All other gaskets must be replaced every five years or earlier as needed.

Old gaskets must be removed completely before installing the new gasket. When replacing gaskets on screws, ensure that the screws are not over tightened. Deformation of the gasket is an indication of suffcient torque. The control and combustion chamber doors have internal seals, replacements must be attached to the same location.

15.1.2Burner and Fan Removal Maintenance

Remove the fan and burner independently to floor level and clean both items internally using a soft brush and compressed air, if available. Take care not to damage the internal parts of the burner. Check fan impeller for cleanliness and free rotation.

The electrodes are an integral part of the burner. To check spark gap, remove the securing screws on the electrode and withdraw it ensuring the gasket is not damaged. Spark gap on electrode should be approximately 3 mm.

15.3 Component Removal

First, isolate the heater from the gas and electricity supply.

Entry to the burner assembly is gained by removing the six door screws and removing the control chamber door. Entry to the combustion chamber is gained by removing the combustion chamber door.

59 of 73

Page 65
Image 65
Roberts Gorden HE45UT, HE20ST, HE50DL, HE30DL, HE50ST, HE35UT, HE50UT, HE45ST, HE25UT, HE40DL, HE60DL, HE70DL Servicing Instructions