BLACKHEAT® HE INSTALLATION OPERATION AND SERVICE MANUAL

3.2 Clearances Data - Linear and Double Linear

NOTE: 1. All dimensions are from the surfaces of all tubes, couplings, tees, elbows and crosses.

2.Clearances B, C and D can be reduced by 50% after 7500 mm of tubing downstream from the burner.

3.All measurements are in millimeters.

FIGURE 3: LINEAR & DOUBLE LINEAR, HORIZONTAL MOUNTS

 

 

 

 

Model

HE15ST HE30DL

HE20ST HE40DL

HE25ST HE50DL

HE30ST HE60DL

HE35ST HE70DL

HE40ST

HE45ST

HE50ST

A

150

150

150

150

150

150

200

200

B

890

970

970

1020

1170

1220

1280

1330

C

1570

1650

1650

1780

1930

1970

2010

2080

D

890

970

970

1020

1170

1220

1280

1330

FIGURE 4: LINEAR & DOUBLE LINEAR, ONE SIDE REFLECTOR

 

 

 

 

A

 

 

Model

HE15ST HE30DL

HE20ST HE40DL

HE25ST HE50DL

HE30ST HE60DL

HE35ST HE70DL

HE40ST

HE45ST

HE50ST

 

 

 

 

 

 

A

150

150

150

150

150

150

200

200

C

B

D

B

230

230

230

230

230

230

230

230

 

 

 

 

 

C

1580

1760

1760

1930

2090

2130

2160

2240

 

 

 

D

1200

1380

1380

1500

1660

1710

1760

1860

FIGURE 5: LINEAR & DOUBLE LINEAR, TWO SIDE REFLECTORS

 

 

 

 

A

 

 

Model

HE15ST HE30DL

HE20ST HE40DL

HE25ST HE50DL

HE30ST HE60DL

HE35ST HE70DL

HE40ST

HE45ST

HE50ST

 

 

 

 

 

 

A

150

150

150

150

150

150

200

200

C

B

D

B

590

640

640

690

820

860

890

1020

 

 

 

 

 

C

1660

1810

1810

1960

2110

2160

2210

2320

 

 

 

D

590

640

640

690

820

860

890

1020

FIGURE 6: LINEAR & DOUBLE LINEAR, 45° MOUNT

 

 

 

 

 

Model

HE15ST HE30DL

HE20ST HE40DL

HE25ST HE50DL

HE30ST HE60DL

HE35ST HE70DL

HE40ST

HE45ST

HE50ST

A

200

200

200

250

250

275

300

300

B

200

200

200

200

200

200

200

200

C

1500

1660

1660

1860

1960

2030

2110

2160

D

1370

1520

1520

1630

1750

1820

1880

2000

6 of 73

Page 12
Image 12
Roberts Gorden HE30UT, HE20ST, HE50DL, HE45UT, HE30DL Clearances Data Linear and Double Linear, Model, HE40ST HE45ST HE50ST