INDOOR UNIT CONTROL CIRCUIT (Continued)
NO. | Item | Overview of specifications | Remarks | ||
8 | Freezing | (1) Performs the following operation control in the COOL or DRY | Tcj : Indoor unit heat | ||
| prevention control | mode according to the Tc (or Tcj) sensor detect temperature. | exchange sensor | ||
| When zone J in the figure below is detected for 6 minutes, the | temp. | |||
| release) | specified operating frequency is decreased from the actual |
| ||
|
| operating frequency, and the specified operating frequency is |
| ||
|
| changed every 30 seconds in zone J. |
|
| |
|
| Timer count stops and is maintained in zone K. |
| ||
|
| Timer count is cleared to restore normal operation when zone I is |
| ||
|
| detected. |
|
|
|
|
| If the specified operating frequency becomes SO due to |
| ||
|
| continuation of zone J, return temperature A is raised from 5 to |
| ||
|
| 12 °C, and operation with L fan speed continues until zone I is |
| ||
|
| detected. |
|
|
|
|
| Tc(˚C) |
|
|
|
|
| 5 | I | A |
|
|
|
|
| K |
|
|
| 2 |
|
|
|
|
|
| J |
|
|
|
| If | Tcn : | ||
|
| conditions become true, freezing prevention control is performed. | Tc after 5 minutes | ||
|
| (However, zone J entering control temperature is changed from 2 | from operation start | ||
|
| to |
|
| Tc |
|
| [Conditions] |
|
| Tc at operation start |
|
| The following A or B becomes true after 5 minutes pass from |
| ||
|
| operation start. |
|
|
|
A
B
9 | (1) Performs the following operation control in the HEAT mode |
|
| |||||||
| control | according to the Tc (or Tcj) sensor detect temperature. |
|
| ||||||
|
| • | When zone M is detected, the specified operating frequency is | This control is disabled for | ||||||
|
|
| decreased from the actual operating frequency, and the specified | twin follower indoor units. | ||||||
|
|
| operating frequency is changed every 30 seconds in zone M. |
| ||||||
|
| • | The specified operating frequency is maintained in zone N. |
| ||||||
|
| • | When zone L is detected, the specified operating frequency is |
| ||||||
|
|
| returned by approx. 6 Hz every 60 seconds. |
|
| |||||
|
| Factory setting |
|
|
| Tc |
|
|
| |
|
| Control temp. (°C) |
| (˚C) | M |
| ||||
|
|
|
|
| Tcj |
| ||||
|
|
|
|
|
|
| A |
| ||
|
|
|
| A | B |
|
|
|
| |
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| N |
|
|
|
|
| 56 (54) | 52 (52) |
|
|
|
| |
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| B |
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| L |
|
|
|
| Note) | At the beginning of operation or when Tc (or Tcj) lowers below | Even when the thermo is | ||||||
|
|
| 30 °C after operation start, values (54) and (52) in the table are | set to OFF, the control is | ||||||
|
|
| used as control temperature. |
|
|
| implemented in the same | |||
|
|
|
|
|
|
|
|
|
| way. |
|
|
|
| |||||||
10 | Residual heat | Runs indoor unit fan in L (low) mode for about 30 seconds after HEAT |
| |||||||
| removal | operation stops to remove residual heat. |
|
|
|
|
– 21 –