NO. | Item |
|
| Overview of specifications |
| Remarks | ||
11 | Flap control | (1) During the first operation after power on, flap position is controlled | Louver angle: 0 °C (full | |||||
|
| automatically according to operation mode (COOL/HEAT). | close) | |||||
|
|
|
|
|
|
|
|
|
|
|
| Cooling | Heating |
|
| Full close |
|
45° | 103° | 0° |
(2)When louver position is controlled by remote controller, the unit’s microcomputer memorizes the position for use in the next operation.
*The memorized louver position is cleared when power is turned off, and returns to the state of (1) above.
|
|
|
|
|
|
| Alarm : A code number | |
(3) Flap position setting |
|
|
|
| (except F08 and | |||
|
|
|
| L31) appears on | ||||
• Flap position can be set within the range below. | ||||||||
the remote | ||||||||
COOL/DRY | HEAT/FAN | |||||||
controller and the | ||||||||
|
|
|
|
|
|
| indoor unit stops. | |
|
|
|
|
|
|
|
|
•Flap position can be set collectively or individually in the group twin or triple operation mode. (Wireless remote controller allows individual setting only.)
(4)Swing setting
•Flap moves within the range below.
All operation modes
•Flap swing range can be set collectively or individually in the group twin or triple operation mode. (Setting by wireless remote controller is disabled when the main remote controller is used.)
(5)When air conditioner operation stops, flap closes automatically. It keeps its position in the event of an alarm.
(6)Flap tilts upward automatically during preparation for heating.
(7)In the twin or triple operation mode selected by wireless remote controller, swing setting interlocks with the header indoor unit. If this setting is transmitted from a follower indoor unit, operation does not change with a reception sound “pi, pi, pi” if operation mode differs between header unit and follower unit.
– 22 –