NO. | Item |
|
| Overview of specifications |
| Remarks | ||||
3 | Room temperature | (2) The set temperature for HEAT operation can be corrected by code Heat intake temperature | ||||||||
| control | No. 06. |
|
|
|
|
|
| shift | |
|
|
|
|
|
|
|
|
|
| (When unit’s temperature |
|
|
| Set data | 0 | 2 | 4 | 6 | |||
|
|
| sensor is used) | |||||||
|
|
|
|
|
|
|
|
|
| |
|
|
| Correction of set temp. | +0°C | +2°C | +4°C | +6°C | |||
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
| Factory setting |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| Set data | 2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
*When use of remote controller sensor is set (with DN32), no correction is performed.
4 | Capacity auto | (1) Issues instruction of operating frequency to outdoor unit according |
| |||||
| control | to the difference between Ta and Ts. |
| |||||
| (GA control) | (2) COOL operation |
|
| ||||
| Calculates room temp. difference between Ta and Ts as well as |
| ||||||
|
| room temp. variation every 90 seconds to find correction value of |
| |||||
|
| specified operating frequency and to correct the current operating |
| |||||
|
| frequency. |
|
|
|
|
| |
|
| : Room temp. difference | n : Number of detection times |
| ||||
|
|
| ||||||
|
|
|
|
|
|
| (90 seconds before) |
|
|
| (3) HEAT operation |
|
| ||||
|
| Calculates room temp. difference between Ta and Ts as well as |
| |||||
|
| room temp. variation every 60 seconds to find correction value of |
| |||||
|
| specified operating frequency and to correct the current operating |
| |||||
|
| frequency. |
|
|
|
|
| |
|
|
| : Room temp. difference | n : Number of detection times |
| |||
|
|
| ||||||
|
|
|
|
|
|
| (60 seconds before) |
|
|
| (4) DRY operation |
|
| ||||
|
| The frequency correction control is the same as that for COOL |
| |||||
|
| operation. |
|
|
|
|
| |
|
| However, the maximum frequency is limited to S6 or so. |
| |||||
|
| Note) When LOW fan speed is set, the maximum frequency is |
| |||||
|
|
| limited to SB or so. |
|
| |||
|
|
|
|
|
|
| ||
5 | COOL/HEAT/ | (1) Switching between COOL and HEAT is determined based on the |
| |||||
| AUTO control | following control. |
|
| ||||
|
| Ta | COOL | After 10 minutes pass from |
| |||
|
| (˚C) |
| |||||
|
| +1.5 |
|
|
|
| thermo sensor OFF, |
|
|
|
|
|
|
| operation mode changes |
| |
|
|
|
|
|
|
|
| |
|
| Tsc |
|
|
| (COOL ON) from HEAT (thermo sensor | Tsc : COOL set temp. | |
|
| or Tsh |
|
| (COOL OFF) |
| OFF) to COOL if Ta exceeds | Tshc : HEAT set temp. + |
|
|
|
|
| Tsh +1.5. | room temp. control/ | ||
|
|
|
|
|
| ( ) shows an example of | correction | |
|
|
|
|
|
|
| ||
|
|
|
|
| HEAT | COOL ON/OFF. |
| |
|
|
|
|
|
|
| After 10 minutes pass from |
|
|
|
|
|
|
|
| thermo sensor OFF, |
|
|
|
|
|
|
|
| operation mode changes |
|
|
|
|
|
|
|
| from COOL (thermo sensor |
|
|
|
|
|
|
|
| OFF) to HEAT if Ta lowers |
|
|
|
|
|
|
|
| below Tsc |
|
(2)The GA control after determination of operation mode follows the description in No. 4.
(3)The room temperature control and temperature correction follow the descriptions in No. 3 and No. 15.
– 18 –