Failure mode detected by outdoor unit (Representative codes)
• The check code used varies depending on the combination with the outdoor unit.
| Diagnosis function |
| Judgment and action | ||
|
|
|
| ||
Check code | Possible causes | Air conditioner status | Conditions | ||
| |||||
|
|
|
|
| |
H01 | Compressor breakdown | OFF | Indicated when an | 1.Check power voltages (200±20 VAC). | |
| • Compressor stops due to |
| error is detected | 2.Freezing cycle overload operation | |
| operating frequency decrease. |
|
| 3.Check current detect circuit on the AC side. | |
|
|
|
|
| |
H02 | Compressor does not work. | OFF | Indicated when an | 1.Failure of compressor (lock, etc.) | |
| • Overcurrent protection circuit is |
| error is detected | ... Replace the compressor. | |
| activated after a certain time from |
|
| 2.Improper compressor wiring (phase loss) | |
| compressor startup. |
|
| ||
|
|
|
| supply | |
|
|
|
|
| |
H03 | Failure of current detect circuit | OFF | Indicated when an | 1.Operation stops soon when restarted. | |
| • Large AC current even during |
| error is detected | ... Check IPDU. | |
| compressor OFF |
|
| ||
| • Phase loss in power supply |
|
| Check | |
|
|
|
|
| |
H06*1 | OFF | Indicated when an | 1.Check freezing cycle (gas | ||
| (applicable models) |
| error is detected | leakage). | |
| COOL : 30 seconds |
|
| 2.Check | |
| HEAT : 10 minutes |
|
| 3.Check outdoor unit CDB board. | |
|
|
|
|
| |
L29 | Other outdoor unit errors | OFF | Indicated when an | 1.Check CDB/IPDU wiring. | |
| • |
| error is detected | 2.Freezing cycle overload operation | |
| (connector disconnection) |
|
|
| |
| • Abnormal heatsink temperature |
|
|
| |
| (over specified value) |
|
|
| |
|
|
|
|
| |
L31*1 | Phase detection protection circuit | Operation | Indicated when an | 1.Check phase sequence, reverse | |
| activated (normal models) | continued | error is detected | phase, and phase loss. | |
|
| (compressor |
| 2.Check outdoor unit boards. | |
|
| OFF) |
| 3.Check | |
|
|
|
| 4.Check | |
|
|
|
|
| |
P03 | Abnormal discharge temperature | OFF | Indicated when an | 1.Check freezing cycle (gas leakage). | |
| (over specified value) |
| error is detected | 2.Failure of electronic expansion valve | |
|
|
|
| 3.Check piping sensor (Td). | |
|
|
|
|
| |
P04 | Failure of | OFF | Indicated when an | 1.Freezing cycle overload operation | |
| (Temperature over specified value |
| error is detected | 2.Check outdoor unit TE sensor. | |
| detected by TE sensor) |
|
| 3.Check outdoor unit CDB board. | |
|
|
| 4.Check | ||
|
|
|
|
| |
P22 | Failure of outdoor unit DC fan | OFF | Indicated when an | 1.Position detect error | |
|
|
| error is detected | 2.Overcurrent protection circuit | |
|
|
|
| operation of outdoor unit fan driver | |
|
|
|
| 3.Outdoor unit fan lock | |
|
|
|
| 4.Check outdoor unit CDB board. | |
|
|
|
|
| |
P26 | Inverter overcurrent protection | OFF | Indicated when an | 1.Operation stops soon when restarted. | |
| circuit activated (short time) |
| error is detected | ... Compressor partial | |
| Main circuit short voltage operation |
|
| 2.Check IPDU for improper wiring. | |
|
|
|
|
| |
P29 | Failure of IPDU position detect | OFF | Indicated when an | 1.The circuit is activated even after | |
| circuit |
| error is detected | compressor’s 3P connector is | |
|
|
|
| disconnected. ...Replace IPDU. | |
|
|
|
|
| |
F04 | Improper mounting, disconnection | OFF | Indicated when an | 1.Check TD. | |
| or |
| error is detected | 2.Check outdoor unit CDB board. | |
| sensor TD |
|
|
| |
|
|
|
|
| |
F06 | Improper mounting, disconnection | OFF | Indicated when an | 1.Check TE, TS. | |
| or |
| error is detected | 2.Check outdoor unit CDB board. | |
| sensor TE, TS |
|
|
| |
|
|
|
|
| |
F08 | Improper mounting, disconnection | Operation | Indicated when an | 1.Check TO. | |
| or | continued | error is detected | 2.Check outdoor unit CDB board. | |
| outside air temp. sensor TO |
|
|
| |
|
|
|
|
|
*1
Fan continues rotating in a failure mode detected by outdoor unit because there is no communication between outdoor unit and follower indoor unit in twin group.