Failure mode detected by outdoor unit (Representative codes)

• The check code used varies depending on the combination with the outdoor unit.

 

Diagnosis function

 

Judgment and action

 

 

 

 

Check code

Possible causes

Air conditioner status

Conditions

 

 

 

 

 

 

H01

Compressor breakdown

OFF

Indicated when an

1.Check power voltages (200±20 VAC).

 

• Compressor stops due to

 

error is detected

2.Freezing cycle overload operation

 

operating frequency decrease.

 

 

3.Check current detect circuit on the AC side.

 

 

 

 

 

H02

Compressor does not work.

OFF

Indicated when an

1.Failure of compressor (lock, etc.)

 

• Overcurrent protection circuit is

 

error is detected

... Replace the compressor.

 

activated after a certain time from

 

 

2.Improper compressor wiring (phase loss)

 

compressor startup.

 

 

3.Lost-phase operation of power

 

 

 

 

supply (3-phase models)

 

 

 

 

 

H03

Failure of current detect circuit

OFF

Indicated when an

1.Operation stops soon when restarted.

 

• Large AC current even during

 

error is detected

... Check IPDU.

 

compressor OFF

 

 

2.Lost-phase operation of power supply

 

• Phase loss in power supply

 

 

Check 3-phase power voltages and wiring.

 

 

 

 

 

H06*1

Low-pressure switch ON

OFF

Indicated when an

1.Check freezing cycle (gas

 

(applicable models)

 

error is detected

leakage).

 

COOL : 30 seconds

 

 

2.Check low-pressure switch circuit.

 

HEAT : 10 minutes

 

 

3.Check outdoor unit CDB board.

 

 

 

 

 

L29

Other outdoor unit errors

OFF

Indicated when an

1.Check CDB/IPDU wiring.

 

CDB-IPDU communication error

 

error is detected

2.Freezing cycle overload operation

 

(connector disconnection)

 

 

 

 

• Abnormal heatsink temperature

 

 

 

 

(over specified value)

 

 

 

 

 

 

 

 

L31*1

Phase detection protection circuit

Operation

Indicated when an

1.Check phase sequence, reverse

 

activated (normal models)

continued

error is detected

phase, and phase loss.

 

 

(compressor

 

2.Check outdoor unit boards.

 

 

OFF)

 

3.Check high-pressure switch.

 

 

 

 

4.Check high-pressure switch circuit wiring.

 

 

 

 

 

P03

Abnormal discharge temperature

OFF

Indicated when an

1.Check freezing cycle (gas leakage).

 

(over specified value)

 

error is detected

2.Failure of electronic expansion valve

 

 

 

 

3.Check piping sensor (Td).

 

 

 

 

 

P04

Failure of high-pressure protection circuit

OFF

Indicated when an

1.Freezing cycle overload operation

 

(Temperature over specified value

 

error is detected

2.Check outdoor unit TE sensor.

 

detected by TE sensor)

 

 

3.Check outdoor unit CDB board.

 

High-pressure switch (normal models)

 

 

4.Check high-pressure switch and circuit.

 

 

 

 

 

P22

Failure of outdoor unit DC fan

OFF

Indicated when an

1.Position detect error

 

 

 

error is detected

2.Overcurrent protection circuit

 

 

 

 

operation of outdoor unit fan driver

 

 

 

 

3.Outdoor unit fan lock

 

 

 

 

4.Check outdoor unit CDB board.

 

 

 

 

 

P26

Inverter overcurrent protection

OFF

Indicated when an

1.Operation stops soon when restarted.

 

circuit activated (short time)

 

error is detected

... Compressor partial short-circuit

 

Main circuit short voltage operation

 

 

2.Check IPDU for improper wiring.

 

 

 

 

 

P29

Failure of IPDU position detect

OFF

Indicated when an

1.The circuit is activated even after

 

circuit

 

error is detected

compressor’s 3P connector is

 

 

 

 

disconnected. ...Replace IPDU.

 

 

 

 

 

F04

Improper mounting, disconnection

OFF

Indicated when an

1.Check TD.

 

or short-circuit of outdoor unit temp.

 

error is detected

2.Check outdoor unit CDB board.

 

sensor TD

 

 

 

 

 

 

 

 

F06

Improper mounting, disconnection

OFF

Indicated when an

1.Check TE, TS.

 

or short-circuit of outdoor unit temp.

 

error is detected

2.Check outdoor unit CDB board.

 

sensor TE, TS

 

 

 

 

 

 

 

 

F08

Improper mounting, disconnection

Operation

Indicated when an

1.Check TO.

 

or short-circuit of outdoor unit

continued

error is detected

2.Check outdoor unit CDB board.

 

outside air temp. sensor TO

 

 

 

 

 

 

 

 

*1 ROA-P*** is not detected by 1HS models.

Fan continues rotating in a failure mode detected by outdoor unit because there is no communication between outdoor unit and follower indoor unit in twin group.