DynaView Interface

Chiller Level Mode

Top Level Mode

Description

 

 

Waiting to Start

The chiller is going through the necessary steps to allow the

 

lead circuit to start.

 

 

Waiting to Start Sub Modes

Description

 

 

Waiting For Condenser Water Flow

The chiller will wait a user adjustable time in this mode for

 

condenser water flow to be established per the flow switch

 

hardwired input.

 

 

 

 

Chiller Level Mode

 

 

 

Top Level Mode

Description

 

 

Running

At least one circuit on the chiller is currently running.

 

 

Running Sub Modes

Description

 

 

Maximum Capacity

The chiller is operating at its maximum capacity.

 

 

Capacity Control Softloading

The control is limiting the chiller loading due to capacity based

 

softloading setpoints.

 

 

Unit is Building Ice

The chiller is Building Ice, and will terminate on the Ice

 

Termination Setpoint based on the Entering Evap Water

 

Temperature sensor.

 

 

 

 

Chiller Level Mode

 

 

 

Top Level Mode

Description

 

 

Running - Limit

At least one circuit on the chiller is currently running, but the

 

operation of the chiller as a whole is being actively limited by

 

the controls. The sub modes that apply to the Running top

 

modes may also be displayed along with the following limit

 

specific modes.

 

 

Running - Limit Sub Modes

Description

 

 

Demand Limit

The number of compressors allowed to operate is being

 

limited to less than the available number of compressors by

 

either the BAS system, the front panel demand limit setpoint

 

or the external demand limit input.

 

 