Trane CCUN 205-211, CGAN 209-214, CH530, CGWN 205-211 manual Diagnostics, CG-SVU02B-E4

Models: CGAN 209-214 CCUN 205-211 CH530 CGWN 205-211

1 36
Download 36 pages 15.91 Kb
Page 28
Image 28
Manual background

Diagnostics

Evaporator Water

Chiller

Warning and

NonLatch

Evap pump

After flow had been proven the chilled water flow input

Remote

Flow Lost Pump 1

 

Special Action

 

commanded on

was open for more than 4 continuous seconds. The

 

(or Pump 2)

 

 

 

 

evaporator pump control will switch control to the

 

 

 

 

 

 

redundant pump. If redundant pump is not available,

 

 

 

 

 

 

diagnostic will clear when flow is established.

 

 

 

 

 

 

 

 

Evaporator Water

Chiller

Warning and

NonLatch

Estab. Evap. Water

Evaporator water flow was not proven within a user

Remote

Flow Overdue

 

Special Action

 

Flow on going from

adjustable time of the evaporator water pump relay being

 

Pump 1 (or

 

 

 

STOP to AUTO.

energized. Diagnostic is reset with return of evaporator

 

Pump 2)

 

 

 

 

water flow.

 

 

 

 

 

 

 

 

Fault Detected:

Chiller

Warning and

NonLatch

All

Detection of a pump fault will cause pump control to

Remote

Evaporator Water

 

Special Action

 

 

switch to the redundant pump.

 

Pump 1 (or

 

 

 

 

 

 

Pump 2)

 

 

 

 

 

 

 

 

 

 

 

 

 

Condenser Water

Chiller

Warning and

NonLatch

Start and All Run

After flow had been proven the condenser water flow

Remote

Flow Lost Pump 1

 

Special Action

 

Modes

input was open for more than 4 continuous seconds. This

 

(or Pump 2)

 

 

 

 

diagnostic is automatically cleared once all circuits are de-

 

 

 

 

 

 

energized.

 

 

 

 

 

 

 

 

Condenser Water

Chiller

Warning and

NonLatch

Estab Cond Water

Condenser water flow was not proven within a user

Remote

Flow Overdue

 

Special Action

 

Flow

adjustable time of the condenser water pump relay being

 

Pump 1 (or

 

 

 

 

energized.

 

Pump 2)

 

 

 

 

 

 

 

 

 

 

 

 

 

Fault Detected:

Chiller

Warning and

NonLatch

All

Detection of a pump fault will cause pump control to

Remote

Condenser Water

 

Special Action

 

 

switch to the redundant pump.

 

Pump 1 (or

 

 

 

 

 

 

Pump 2)

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan Fault

Circuit

Warning

NonLatch

All

The fan fault input was open for more than 5 seconds.

Local

 

 

 

 

 

 

 

High Condensing

Chiller

Warning

Latch

Running

When running in parallel pump control, with one pump

Remote

Pressure Pump

 

 

 

 

on, a high condensing pressure will force add the second

 

Add

 

 

 

 

pump. It will latch on to prevent pump cycling.

 

 

 

 

 

 

 

 

28

CG-SVU02B-E4

Page 28
Image 28