DynaView Interface

Chiller Level Mode

Top Level Mode

Description

 

 

Shutting Down

The chiller is still running but shutdown is imminent. The

 

chiller is going through a compressor run-unload.

 

 

Shutting Down Sub Modes

Description

 

 

Evaporator Water Pump Off Delay:

The Evaporator pump is executing the pump off delay timer.

MIN:SEC

 

 

 

Condenser Water Pump Off Delay:

The Condenser pump is executing the pump off delay timer.

MIN:SEC

 

 

 

 

 

Chiller Level Mode

 

 

 

Top Level Mode

Description

 

 

Misc.

These sub modes may be displayed in most of the top level

 

chiller modes

 

 

Misc. Sub Modes

Description

 

 

Cond Fans Inhibited By Low Pressure

The condenser fans are being inhibited from running because

 

the ambient temperature was below 10°C and the suction

 

pressure status is not good at startup for each circuit.

 

 

Hot Water Control

For water cooled (CGWN) the chiller is controlling to the

 

leaving condenser water temperature. For a reversible (CXAN)

 

the reversing valve is in the heating position. This sub-mode is

 

mutually exclusive with the Chilled Water Control mode.

 

 

Chilled Water Control

For water cooled (CGWN) the chiller is controlling to the

 

leaving evaporator water temperature. For a reversible (CXAN)

 

the reversing valve is in the cooling position. This sub-mode is

 

mutually exclusive with the Hot Water Control mode

 

 

Manual Evaporator Pump Override

The evaporator water pump relay is on due to a manual

 

command.

 

 

Diagnostic Evap Pump Override

The evaporator water pump relay is on due to a diagnostic.

 

 

Diagnostic Condenser Fan Override

The condenser fan relays are on due to a diagnostic.

 

 

Manual Condenser Pump Override

The condenser water pump relay is on due to a manual

 

command.

 

 

Manual Compressor Control Signal

Chiller capacity control is being controlled by DynaView or

 

TechView.

 

 

Anti-Freeze Heater On

The anti-freeze heater is on.

 

 