DynaView Interface
Circuit Level Mode
Top Level Mode | Description |
|
|
Running - Limit | The compressor on the given circuit is currently running in a |
| limit mode. |
|
|
Running - Limit Sub Modes | Description |
|
|
Hot Start Limit | Additional stages on a given circuit are being held off based |
| on leaving evaporator temperature. |
|
|
Condenser Pressure Limit | The circuit is being inhibited from loading due to high |
| condenser pressure. |
|
|
Low Evaporator Pressure Limit | The circuit is being inhibited from loading due to low |
| evaporator pressure. |
|
|
|
|
Circuit Level Mode |
|
|
|
Top Level Mode | Description |
|
|
Preparing Shutdown | The circuit is preparing to |
|
|
Preparing Shutdown Sub Modes | Description |
|
|
Operational Pumpdown | The operational pumpdown is enabled and the circuit is |
| shutting down. |
|
|
|
|
Circuit Level Mode |
|
|
|
Top Level Mode | Description |
|
|
Shutting Down | The chiller is going through the necessary steps after de- |
| energizing the compressor. |
|
|
Shutting Down Sub Modes | Description |
|
|
| No Circuit |
|
|
|
|
Circuit Level Mode |
|
|
|
Top Level Mode | Description |
|
|
Misc. | These sub modes may be displayed in most of the top level |
| circuit modes |
|
|
Misc. Sub Modes | Description |
|
|
Defrosting | The circuit is in a defrost operational mode. |
|
|
Service Pumpdown | The circuit is currently performing a service pumpdown. |
|
|
Compressor X Running | A specific compressor is running where X is A or B. |
|
|
Restart Time Inhibit Cprsr X: MIN:SEC | If there is accumulated Restart Inhibit Time, it must expire |
| before the compressor is allowed to start. X is denoted as |
| compressor A or B. |
|
|
15 |