Trane CH530, CCUN 205-211, CGAN 209-214, CGWN 205-211 manual Diagnostics, CG-SVU02B-E4

Models: CGAN 209-214 CCUN 205-211 CH530 CGWN 205-211

1 36
Download 36 pages 15.91 Kb
Page 26
Image 26
Manual background

Diagnostics

Evaporator Entering Water

Chiller

Normal

Latch

All

Bad Sensor or LLID

Remote

Temp Sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

Evaporator Leaving Water

Chiller

Normal

Latch

All

Bad Sensor or LLID

Remote

Temp Sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

Condenser Entering Water

Chiller

Warning

Latch

All

Bad Sensor or LLID

Remote

Temp Sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

Condenser Leaving Water

Chiller

Warning

Latch

All

Bad Sensor or LLID

Remote

Temp Sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

Discharge Pressure

Circuit

Normal

Latch

All

Bad Sensor or LLID

Remote

Transducer

 

 

 

 

 

 

 

 

 

 

 

 

 

Suction Pressure Transducer

Circuit

Immediate

Latch

All

Bad Sensor or LLID

Remote

 

 

 

 

 

 

 

Suction Temperature Sensor

Circuit

Normal

Latch

All

Bad Sensor or LLID

Remote

 

 

 

 

 

 

 

Evaporator Protection Water

Circuit

Normal

Latch

All

Bad Sensor or LLID

Remote

Temp Sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

Low Evap Leaving Water

Chiller or

Warning

NonLatch

Unit in Stop

a) The leaving chilled water temperature fell below the leaving

Remote

Temp: Unit Off

Circuit

and Special

 

Mode, or in

water temp cutout setting for 16.6°C- seconds while the Chiller

 

 

 

Action

 

Auto Mode

is in the Stop mode, or in Auto mode with no compressors

 

 

 

 

 

and No

running. Energize Evap Water pump Relay until diagnostic auto

 

 

 

 

 

Ckt(s)

resets, then return to normal evap pump control. Automatic

 

 

 

 

 

Energized

reset occurs when the temp rises 1.1°C above the cutout

 

 

 

 

 

[Any Ckt

setting for 30 minutes. When this diagnostic is active AND

 

 

 

 

 

Energized]

Leaving Water Temperature sensor diagnostic (loss of comm or

 

 

 

 

 

 

out of range) the Evap Water pump relay shall be de-energized.

 

 

 

 

 

 

b) If evaporator protection temperature sensors are installed,

 

 

 

 

 

 

the effect is on the appropriate circuit. Else, the effect is on the

 

 

 

 

 

 

chiller.

 

 

 

 

 

 

 

 

Low Evap Leaving Water

Chiller or

Immediate

NonLatch

Any Ckt[s]

a) The chilled water temperature fell below the cutout setpoint

Remote

Temp: Unit On

Circuit

and Special

 

Energized

for 16.6°C-seconds while a compressor was running.

 

 

 

Action

 

[No Ckt(s)

Automatic reset occurs when the temperature rises 1.1°C

 

 

 

 

 

Energizd]

above the cutout setting for 2 minutes. This diagnostic shall not

 

 

 

 

 

 

de-energize the Evaporator Water Pump Output. If this

 

 

 

 

 

 

diagnostic is active the Low Evap Leaving Water Temp: Unit Off

 

 

 

 

 

 

diagnostic shall be suppressed.

 

 

 

 

 

 

b) If evaporator protection temperature sensors are installed,

 

 

 

 

 

 

the effect is on the appropriate circuit. Else, the effect is on the

 

 

 

 

 

 

chiller.

 

 

 

 

 

 

 

 

Low Refrigerant

Circuit

Immediate

Latch

All except

The Evaporator Saturated Refrigerant Temperature dropped

Local

Temperature

 

 

 

[Service

below the Low Refrigerant Temperature Cutout Setpoint for

 

 

 

 

 

Pumpdown]

16.6°C-seconds.

 

 

 

 

 

 

 

 

26

CG-SVU02B-E4

Page 26
Image 26
Trane CH530, CCUN 205-211, CGAN 209-214, CGWN 205-211 manual Diagnostics, CG-SVU02B-E4