Table 6 - Communication Diagnostics

Diagnostics

Table 6 - Communication Diagnostics

Notes:

1.The following communication loss diagnostics will not occur unless that input or output is required to be present by the particular configuration and installed options for the chiller.

2.Communication diagnostics (with the exception of "Excessive Loss of Comm" are named by the Functional Name of the input or output that is no longer being heard from by the Main Processor.

Many LLIDs, such as the Quad Relay LLID, have more than one functional output associated with it. A comm loss with such a multiple function board will generate multiple diagnostics. Refer to the Chiller's wiring diagrams to relate the occurrence of multiple communication diagnostics back to the physical llid boards that they have been assigned to (bound).

Diagnostic Name

Effects

Severity

Persistence

Active

Criteria

Reset

 

 

 

 

Modes

 

Level

 

 

 

 

[Inactive

 

 

 

 

 

 

Modes]

 

 

 

 

 

 

 

 

 

Excessive Loss of Comm

Chiller

Immediate

Latch

All

Loss of comm with 20% or more of the llids configured for the

Remote

 

 

 

 

 

system has been detected. This diagnostic will suppress the

 

 

 

 

 

 

callout of all subsequent comm loss diagnostics. Check power

 

 

 

 

 

 

supply(s) and power disconnects - troubleshoot LLIDS buss

 

 

 

 

 

 

using TechView

 

 

 

 

 

 

 

 

Comm Loss:

Chiller

Normal

Latch

All

Continual loss of communication between the MP and the

Remote

External Auto/Stop

 

 

 

 

Functional ID has occurred for a 35-40 second period.

 

 

 

 

 

 

 

 

Comm Loss:

Chiller

Normal

Latch

All

Continual loss of communication between the MP and the

Remote

Emergency Stop

 

 

 

 

Functional ID has occurred for a 35-40 second period.

 

 

 

 

 

 

 

 

Comm Loss:

Chiller

Warning

Latch

All

Continual loss of communication between the MP and the

Remote

Ext Ice Building Ctrl Input

 

 

 

 

Functional ID has occurred for a 35-40 second period. Chiller

 

 

 

 

 

 

shall revert to normal (non-ice building) mode regardless of last

 

 

 

 

 

 

state.

 

 

 

 

 

 

 

 

Comm Loss:

Chiller

Warning

Latch

All

Continual loss of communication between the MP and the

Remote

Outdoor Air Temperature

 

 

 

 

Functional ID has occurred for a 35-40 second period. If

 

 

 

 

 

 

configured as an air-cooled this diagnostic shall turn on all fans

 

 

 

 

 

 

and use a minimum LPC ignore time of 30 seconds.

 

 

 

 

 

 

 

 

Comm Loss:

Chiller

Normal

Latch

All

Continual loss of communication between the MP and the

Remote

Evap Leaving Water Temp

 

 

 

 

Functional ID has occurred for a 35-40 second period.

 

 

 

 

 

 

 

 

Comm Loss:

Chiller

Normal

Latch

All

Continual loss of communication between the MP and the

Remote

Evap Entering Water Temp

 

 

 

 

Functional ID has occurred for a 35-40 second period.

 

 

 

 

 

 

 

 

Comm Loss:

Chiller

Warning

Latch

All

Continual loss of communication between the MP and the

Remote

Condenser Leaving Water

 

 

 

 

Functional ID has occurred for a 35-40 second period.

 

Temp

 

 

 

 

 

 

 

 

 

 

 

 

 

Comm Loss:

Chiller

Warning

Latch

All

Continual loss of communication between the MP and the

Remote

Condenser Entering Water

 

 

 

 

Functional ID has occurred for a 35-40 second period.

 

Temp

 

 

 

 

 

 

 

 

 

 

 

 

 

Comm Loss:

Circuit

Normal

Latch

All

Continual loss of communication between the MP and the

Remote

Discharge Pressure

 

 

 

 

Functional ID has occurred for a 35-40 second period.

 

Transducer

 

 

 

 

 

 

 

 

 

 

 

 

 

CG-SVU02B-E4

29