Step 9. Programmable

Installation

Step 9. Programmable

Settings

The controller has a total of six (7) parameters that are user- configurable:

1.Vent Door Configuration

2.Indoor Fan Cycle configuration

3.Temperature Setpoint Limiting configuration

4.Energy Management Setpoint Offset configuration

5.Display Units configuration

6.Indoor Temperature Calibration

7.DH Offset

The interface module texts “SETTING” and “STEP” provide user feedback when the unit is in the configuration mode. The number directly above the word “STEP” indicates the configuration step that is being adjusted. The numbers above the word “SETTING” (XX.x) indicate the value of the parameter.

In order for the user to access the configurable parameters, a digital display module must be present.

The configuration set-up mode is entered by pressing and holding the "MODE" and "FAN" buttons simultaneously for 5 seconds.

Table 9.

Set point configuration

 

 

 

 

 

Configuration

Configuration

 

step

Step description

setting

Setting description

 

 

 

 

1

Ventilation Enable

0

Ventilation is disabled

 

 

1 (default)

 

 

 

Ventilation is enabled

 

 

 

 

 

 

 

 

 

0 (default)

Cycle with compressor

2

Indoor fan cycle

1

continuously, OFF in OFF mode

 

 

ON continuously, HIGH in OFF

 

 

 

 

 

2

mode

 

 

 

 

 

Temperature

0 (default)

cool 50 - 90°F, heat 50 - 90°F

 

1

cool 55 - 90°F, heat 50 - 85°F

3

Setpoint Limits

 

 

 

 

2

cool 60 - 90°F, heat 50 - 80°F

 

 

3

cool 65 - 90°F, heat 50 - 75°F

 

 

 

 

 

 

Default: 10°F (5.5°C)

 

 

 

Range: 0 to 20°F

 

4

Energy

(0.0 to 10.0°C)

 

 

Management

Resolution: 1.0°F

 

 

 

 

 

 

(0.5°C)

 

 

 

 

 

5

Display units

0 (default)

IP (English)

 

1

SI (Metric)

 

 

 

 

 

 

 

 

Default: 0°F (0.0°C)

 

 

 

Range: -9 to 9°F

 

6

Indoor

(-5.0 to 5.0°C)

 

 

Temperature

Resolution: 1.0°F

 

 

Calibration

 

 

 

(0.5°C)

 

 

 

 

 

 

 

Default: 1°F (0.5°C)

 

 

 

Range: 0 to 2°F

 

7

DH offset

(0.0 to 1.0°C)

 

 

 

Resolution 1.0°F

Value of zero disables DH.

 

 

(0.5°C)

 

 

 

 

 

PTAC-SVX01C-EN