Trane PTAC-SVX01C-EN Installation, PTEE manual test sequence, PTHE manual test sequence

Models: PTAC-SVX01C-EN

1 52
Download 52 pages 2.5 Kb
Page 20
Image 20
Table 14. PTEE manual test sequence

Installation

Table 14. PTEE manual test sequence

 

 

Indoor

Indoor

Remote

Outdoor

Condensate

 

Reversing

 

Ventilation

Time in

Step

 

Fan High

Fan Low

Fan

Fan

Pump

Comp

Valve

Aux. Heat

Door/Fan

Step

 

 

 

 

 

 

 

 

 

 

 

 

1

All off

Off

Off

Off

Off

N/A (Off)

Off

N/A (Off)

Off

Off

10 sec

 

 

 

 

 

 

 

 

 

 

 

 

2

Fan high

On

Off

Off

Off

N/A (Off)

Off

N/A (Off)

Off

Off

20 sec

 

 

 

 

 

 

 

 

 

 

 

 

3

Fan Low

Off

On

Off

Off

N/A (Off)

Off

N/A (Off)

Off

Off

20 sec

 

 

 

 

 

 

 

 

 

 

 

 

4

Remote

Off

On

On

Off

N/A (Off)

Off

N/A (Off)

Off

Off

20 sec

 

Fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

Outdoor

Off

On

Off

On

N/A (Off)

Off

N/A (Off)

Off

Off

20 sec

 

Fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

Compres

Off

On

Off

On

N/A (Off)

On

N/A (Off)

Off

Off

60 sec

 

sor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

Aux Heat

Off

On

Off

OnOff

N/A (Off)

Off

N/A (Off)

On

Off

60 sec

 

 

 

 

 

 

 

 

 

 

 

 

8

Vent

Off

On

Off

OnOff

N/A (Off)

Off

N/A (Off)

Off

On

20 sec

 

Door

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Exit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 15. PTHE manual test sequence

 

 

Indoor

Indoor

Remote

Outdoor

Condensate

 

Reversing

Aux

Ventilation

Time in

Step

 

Fan High

Fan Low

Fan

Fan

Pump

Comp

Valve

Heat

Door/Fan

Step

 

 

 

 

 

 

 

 

 

 

 

 

1

All off

Off

Off

Off

Off

Off

Off

Off

Off

Off

10 sec

 

 

 

 

 

 

 

 

 

 

 

 

2

Fan High

On

Off

Off

Off

Off

Off

Off

Off

Off

20 sec

 

 

 

 

 

 

 

 

 

 

 

 

3

Fan Low

Off

On

Off

Off

Off

Off

Off

Off

Off

20 sec

 

 

 

 

 

 

 

 

 

 

 

 

4

Remote Fan

Off

On

On

Off

Off

Off

Off

Off

Off

20 sec

 

 

 

 

 

 

 

 

 

 

 

 

5

Outdoor Fan

Off

On

Off

On

Off

Off

Off

Off

Off

20 sec

 

 

 

 

 

 

 

 

 

 

 

 

6

Condensate

Off

On

Off

On

On1

Off

Off

Off

Off

20 sec

 

Pump

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

Compressor

Off

On

Off

On

Off

On

OffOn

Off

Off

60 sec

 

on Cooling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

Compressor

Off

Off

On

Off

On

Off

Off

OffOn

Off

60 sec

 

Off

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

Compressor

Off

On

Off

On

Off

On

OnOff

Off

Off

60 sec

 

on Heating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

Aux Heat

Off

On

Off

OnOff

Off

Off

OnOff

On

Off

60 sec

 

 

 

 

 

 

 

 

 

 

 

 

11

Vent Door

Off

On

Off

OnOff

Off

Off

Off

Off

On

20 sec

 

 

 

 

 

 

 

 

 

 

 

 

Exit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

PTAC-SVX01C-EN

Page 20
Image 20
Trane PTAC-SVX01C-EN Installation, PTEE manual test sequence, PTHE manual test sequence