Installation

Table 5.

Unit power supply

 

 

 

 

 

 

 

 

Voltage

 

Options

 

Accessory

Accessory part number

 

 

 

 

 

 

115V

 

 

 

 

 

 

 

 

 

 

 

 

 

Required:

 

Universal Power Cord 15

BAYPCRD007

Option 1.

 

 

 

Amp

 

 

 

 

 

 

 

 

 

 

 

A field supplied 115 volt 15 amp receptacle is mounted

 

 

 

 

in the building floor or wall. A Trane 115 volt 15 amp

 

 

 

 

power cord BAYPCRD007 is connected to the PTAC and

 

 

 

 

plugged into the receptacle.

 

 

 

 

 

 

 

 

Required:

 

Universal Power Cord 15

BAYPCRD007

Option 2.

 

 

 

Amp

 

 

 

 

 

 

 

 

 

 

 

Universal Subbase

BAYSUB001

 

 

 

 

 

 

 

 

 

 

A Trane subbase BAYSUB001 is attached to the wall

 

 

 

 

sleeve. A field supplied 115 volt 15 amp receptacle is

 

 

 

 

mounted into the subbase. A Trane 115 volt 15 amp

 

 

 

 

power cord BAYPCRD007 is connected to the PTAC and

 

 

 

 

plugged into the receptacle

 

 

 

 

 

 

Option 3.

 

Required:

 

Hard Wire Kit

BAYHWRK001

 

 

 

 

 

 

 

 

 

 

Connector for Hardwire

BAYCNHK031

 

 

 

 

Kit for 15 Amp

 

 

 

 

 

 

 

 

 

 

 

A Trane hardwire kit BAYHRK001 is direct wired to the

 

 

 

 

building power supply and attached to the PTAC. A

 

 

 

 

Trane connector kit BAYCNHK031 is connected to the

 

 

 

 

PTAC and connected to the hard wire kit in the unit

 

 

 

 

mounted junction box

 

 

 

 

 

 

 

265 V

 

 

 

 

 

 

 

 

 

 

 

Option 1.

 

Required:

 

Universal Subbase

BAYSUB001

 

 

 

 

 

 

 

 

 

 

Socket for subbase 20 or

BAYSCKT003, BAYSCKT004

 

 

 

 

30 Amp

 

 

 

 

 

 

 

 

 

 

 

Universal Power Cord

BAYPCRD004, BAYPCRD005,

 

 

 

 

15,20 or 30 Amp

BAYPCRD006

 

 

 

 

 

 

 

 

 

 

Fuses 15, 20 or 30 Amp

BAYFUSE001, BAYFUSE002,

 

 

 

 

 

BAYFUSE003

 

 

 

 

 

 

 

 

Optional

 

Power Switch

BAYPSW002

 

 

 

 

 

 

Option 2.

 

Required:

 

Hard Wire Kit

BAYHWRK001

 

 

 

 

 

 

 

 

 

 

Connector for Hardwire

BAYCNHK021, BAYCNHK022 ,

 

 

 

 

Kit for 15, 20 or 30 Amp

BAYCNHK023

 

 

 

 

 

 

 

 

Optional

 

Power Switch if 30 Amp

BAYPSW002

 

 

 

 

 

230/ 208 V

 

 

 

 

 

 

 

 

 

 

Option 1.

 

Required:

 

Universal Power Cord

BAYPCRD001, BAYPCRD002,

 

 

 

 

15,20 or 30 Amp

BAYPCRD003

 

 

 

 

 

 

 

 

Optional

 

Power Switch

BAYPSW002

 

 

 

 

 

 

Option 2.

 

Required:

 

Universal Subbase

BAYSUB001

 

 

 

 

 

 

 

 

 

 

Socket for subbase 20

BAYSCKT001, BAYSCKT002

 

 

 

 

or 30 Amp

 

 

 

 

 

 

 

 

 

 

 

Universal Power Cord

BAYPCRD001, BAYPCRD002,

 

 

 

 

15,20 or 30 Amp

BAYPCRD003

 

 

 

 

 

 

 

 

Optional

 

Circuit Breaker 15, 20 or

BAYCBKR001, BAYCBKR002,

 

 

 

 

30 Amp

BAYCBKR003

 

 

 

 

 

 

 

 

 

 

Power Switch

BAYPSW002

 

 

 

 

 

 

Option 3.

 

Required:

 

Hard Wire Kit

BAYHWRK001

 

 

 

 

 

 

 

 

 

 

Connector for Hardwire

BAYCNHK011, BAYCNHK012,

 

 

 

 

Kit for 15, 20 or 30 Amp

BAYCNHK013

 

 

 

 

 

 

 

 

Optional

 

Power Switch

BAYPSW002

 

 

 

 

 

 

1.All units required either a power cord or hard wire kit to power the unit

2.The Hydronic chassis "W" ships with no electric heat

3.All Hydronic Chassis "W" units required a power cord

4.All 265volt Hydronic chassis "W" required subbase, fuses and socket.

Step 7. Install the unit controls.

The PTAC controller’s normal operation can be operated by using either

Display module - can be wall- mounted or unit mounted.

Remote Class 2 thermostat -

For Remote Class 2 Thermostat Installation, read installation, operation, and maintenance booklet carefully.

Look in Wiring Diagram section for information on wiring.

If a remote thermostat is connected, the unit's display will not be present and the controller's normal space temperature control functionality is overridden by the remote device.

When the controller is being directed by a remote thermostat, the following inputs/functions are disabled or not present:

1.User display inputs (setpoint/ mode/fan)

2.Dehumidification

3.Configuration setup (indoor fan, setpoint limits, EMS offset, display units)

4.Energy management system

5.Manual Test

Unit functions that remain under direct supervision of the controller are:

1.Random Restart

2.Heat Pump OAT switchover

3.Tubing burst protection

4.Room freeze protection

5.Indoor coil freeze protection

6.Defrost control

When connected to a remote thermostat, the controller interprets the combination of thermostat inputs as its operating mode and behaves accordingly.

It is recommended to use a small screwdriver to gently pryt the removable treminal block "TB2" up and off for easy connection.

14

PTAC-SVX01C-EN

Page 14
Image 14
Trane PTAC-SVX01C-EN Install the unit controls, Voltage Options Accessory Accessory part number 115V, 230/ 208 Option

PTAC-SVX01C-EN specifications

The Trane PTAC-SVX01C-EN is a cutting-edge Packaged Terminal Air Conditioner (PTAC) designed to provide optimal temperature control, energy efficiency, and user comfort in a variety of settings, including hotels, apartments, and office buildings. This unit stands out with its robust features and advanced technologies, making it a reliable choice for meeting diverse heating and cooling needs.

At the heart of the Trane PTAC-SVX01C-EN is its innovative design, which combines powerful performance with quiet operation. This unit utilizes a high-efficiency compressor that ensures rapid cooling and heating, providing ideal comfort regardless of the external climate. With a capacity range suitable for smaller spaces, the PTAC delivers strong performance while maintaining energy efficiency, thus reducing operational costs over time.

One of the key characteristics of the PTAC-SVX01C-EN is its user-friendly interface. The intuitive controls allow users to effortlessly adjust temperature settings, fan speeds, and modes of operation, including cooling, heating, and fan only. This flexibility enhances user comfort while optimizing energy consumption. Additionally, the unit features a programmable timer, enabling users to schedule operation according to their specific needs, further conserving energy when spaces are unoccupied.

The unit's Quiet Operation Technology minimizes noise levels, making it an ideal choice for environments where peace and quiet are paramount. This feature is particularly beneficial in hospitality settings, where guests expect a tranquil atmosphere. The PTAC is engineered to provide ample airflow while minimizing sound, creating a pleasant indoor environment.

Another standout feature of the Trane PTAC-SVX01C-EN is its advanced air filtration system. The integrated filter effectively captures dust, allergens, and other airborne particles, promoting a cleaner and healthier living environment. This is particularly essential for individuals with allergy sensitivities or respiratory issues.

Durability is also a hallmark of the PTAC-SVX01C-EN. Built with high-quality materials, it is designed to withstand the demands of continuous operation while requiring minimal maintenance. The unit's sleek and compact design allows for easy installation in various locations, ensuring versatility without sacrificing performance.

In summary, the Trane PTAC-SVX01C-EN represents a perfect blend of efficiency, comfort, and innovative technology. Its user-friendly controls, quiet operation, and advanced air filtration make it a leading choice for those seeking reliable climate control solutions in residential and commercial spaces alike. Whether for heating or cooling, the Trane PTAC-SVX01C-EN is engineered to deliver exceptional performance and lasting dependability.