Installation
Note: If using a third party thermostat to control the unit, the thermostat must have a clearly marked OFF state or position.
Note: It is important to make sure that the control board’s fuse is functioning. The specs for the control board fuse are:
5x20mm, 250V, 315mA, fast acting. For more inormation on a blown fuse on the control board, check the Troubleshooting section of this document.
Table 6. Maximum wire length for front desk switch and remote control connections
|
| Wire |
| Specification | |
|
|
|
External Interface | Size | Length |
|
|
|
| #22 | 100 ft. |
|
|
|
Thermostat | #20 | 200 ft |
|
| |
| #18 | 300 ft. |
|
|
|
Energy mgmt system | #20 | 900 ft. |
|
|
|
| #18 | 1500 ft. |
|
|
|
Remote fan | #20 | 60 ft. |
|
|
|
| #18 | 66 ft. |
|
|
|
Display module | #20 | 100 ft. |
|
|
|
| #18 | 120 ft. |
|
|
|
Table 7. | Wiring Voltage |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| Voltage at terminal |
| Corresponding | ||||
| Unit | Mode |
|
|
|
|
|
| Normal |
|
|
|
|
|
|
| |||
| GH | GL | W | Y |
| O | Operation | ||
|
|
|
|
|
|
|
|
|
|
|
| High Heat Pump | 24 | 0 | 0 | 24 |
| 0 | Heat |
|
|
|
|
|
|
|
|
|
|
|
| High Auxiliary Heat | 24 | 0 | 24 | 0 |
| X | Heat |
|
|
|
|
|
|
|
|
|
|
|
| Low Auxiliary Heat | 0 | 24 | 24 | 0 |
| X | Heat |
PTEE Air Conditioner |
|
|
|
|
|
|
|
| |
High Cooling | 24 | 0 | 0 | 24 |
| X | Cool | ||
(Auxiliary is Electric, |
|
|
|
|
|
|
|
| |
Low Cooling | 0 | 24 | 0 | 24 |
| X | Cool | ||
Hot Water, or Steam |
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
| High Fan | 24 | 0 | 0 | 0 |
| X | Fan Only |
|
|
|
|
|
|
|
|
|
|
|
| Low Fan | 0 | 24 | 0 | 0 |
| X | Fan Only |
|
|
|
|
|
|
|
|
|
|
|
| Off | 0 | 0 | 0 | 0 |
| X | Off – no capacity |
|
|
|
|
|
|
|
|
|
|
Notes: In the event that none of the combinations listed in the table above is present, the input will be deemed invalid and all heating, cooling, and fan operation will be disabled.
Table 7. | Wiring Voltage |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| Voltage at terminal |
| Corresponding | ||||
| Unit | Mode |
|
|
|
|
|
| Normal |
|
|
|
|
|
|
| |||
| GH | GL | W | Y |
| O | Operation | ||
|
|
|
|
|
|
|
|
|
|
|
| High Heat Pump | 24 | 0 | 0 | 24 |
| 0 | Heat |
|
|
|
|
|
|
|
|
|
|
|
| Low Heat Pump | 0 | 24 | 0 | 24 |
| 0 | Heat |
|
|
|
|
|
|
|
|
|
|
|
| High Emgcy Heat | 24 | 0 | 24 | 0 |
| 0 | Heat |
|
|
|
|
|
|
|
|
|
|
|
|
| 24 | 0 | 24 | 24 |
| 0 | Electric Heat Only |
|
|
|
|
|
|
|
|
| |
PTHE Heat Pump | Low Emgcy Heat | 0 | 24 | 24 | 0 |
| 0 | Heat | |
Auxiliary is Electric |
|
|
|
|
|
|
|
| |
| 0 | 24 | 24 | 24 |
| 0 | Electric Heat Only | ||
only |
|
|
| ||||||
|
|
|
|
|
|
|
|
| |
|
| High Cooling | 24 | 0 | 0 | 24 |
| 24 | Cool |
|
|
|
|
|
|
|
|
|
|
|
| Low Cooling | 0 | 24 | 0 | 24 |
| 24 | Cool |
|
|
|
|
|
|
|
|
|
|
|
| High Fan | 24 | 0 | 0 | 0 |
| 0 | Fan Only |
|
|
|
|
|
|
|
|
|
|
|
| Low Fan | 0 | 24 | 0 | 0 |
| 0 | Fan Only |
|
|
|
|
|
|
|
|
|
|
|
| Off | 0 | 0 | 0 | 0 |
| 0 | Off – no capacity |
|
|
|
|
|
|
|
|
|
|