Wiring Voltage

Installation

Note: If using a third party thermostat to control the unit, the thermostat must have a clearly marked OFF state or position.

Note: It is important to make sure that the control board’s fuse is functioning. The specs for the control board fuse are:

5x20mm, 250V, 315mA, fast acting. For more inormation on a blown fuse on the control board, check the Troubleshooting section of this document.

Table 6. Maximum wire length for front desk switch and remote control connections

 

 

Wire

 

Specification

 

 

 

External Interface

Size

Length

 

 

 

 

#22

100 ft.

 

 

 

Thermostat

#20

200 ft

 

 

 

#18

300 ft.

 

 

 

Energy mgmt system

#20

900 ft.

 

 

 

 

#18

1500 ft.

 

 

 

Remote fan

#20

60 ft.

 

 

 

 

#18

66 ft.

 

 

 

Display module

#20

100 ft.

 

 

 

 

#18

120 ft.

 

 

 

Table 7.

Wiring Voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage at terminal

 

Corresponding

 

Unit

Mode

 

 

 

 

 

 

Normal

 

 

 

 

 

 

 

 

GH

GL

W

Y

 

O

Operation

 

 

 

 

 

 

 

 

 

 

 

 

High Heat Pump

24

0

0

24

 

0

Heat

 

 

 

 

 

 

 

 

 

 

 

 

High Auxiliary Heat

24

0

24

0

 

X

Heat

 

 

 

 

 

 

 

 

 

 

 

 

Low Auxiliary Heat

0

24

24

0

 

X

Heat

PTEE Air Conditioner

 

 

 

 

 

 

 

 

High Cooling

24

0

0

24

 

X

Cool

(Auxiliary is Electric,

 

 

 

 

 

 

 

 

Low Cooling

0

24

0

24

 

X

Cool

Hot Water, or Steam

 

 

 

 

 

 

 

 

 

 

 

 

 

High Fan

24

0

0

0

 

X

Fan Only

 

 

 

 

 

 

 

 

 

 

 

 

Low Fan

0

24

0

0

 

X

Fan Only

 

 

 

 

 

 

 

 

 

 

 

 

Off

0

0

0

0

 

X

Off – no capacity

 

 

 

 

 

 

 

 

 

 

Notes: In the event that none of the combinations listed in the table above is present, the input will be deemed invalid and all heating, cooling, and fan operation will be disabled.

Table 7.

Wiring Voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage at terminal

 

Corresponding

 

Unit

Mode

 

 

 

 

 

 

Normal

 

 

 

 

 

 

 

 

GH

GL

W

Y

 

O

Operation

 

 

 

 

 

 

 

 

 

 

 

 

High Heat Pump

24

0

0

24

 

0

Heat

 

 

 

 

 

 

 

 

 

 

 

 

Low Heat Pump

0

24

0

24

 

0

Heat

 

 

 

 

 

 

 

 

 

 

 

 

High Emgcy Heat

24

0

24

0

 

0

Heat

 

 

 

 

 

 

 

 

 

 

 

 

 

24

0

24

24

 

0

Electric Heat Only

 

 

 

 

 

 

 

 

 

PTHE Heat Pump

Low Emgcy Heat

0

24

24

0

 

0

Heat

Auxiliary is Electric

 

 

 

 

 

 

 

 

 

0

24

24

24

 

0

Electric Heat Only

only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High Cooling

24

0

0

24

 

24

Cool

 

 

 

 

 

 

 

 

 

 

 

 

Low Cooling

0

24

0

24

 

24

Cool

 

 

 

 

 

 

 

 

 

 

 

 

High Fan

24

0

0

0

 

0

Fan Only

 

 

 

 

 

 

 

 

 

 

 

 

Low Fan

0

24

0

0

 

0

Fan Only

 

 

 

 

 

 

 

 

 

 

 

 

Off

0

0

0

0

 

0

Off – no capacity

 

 

 

 

 

 

 

 

 

 